Samsung UPC3240C Installation Method, Installation Procedures, When using the anchor bolt

Models: APC3240C UPC3240C

1 36
Download 36 pages 52.33 Kb
Page 28
Image 28
INSTALLATION METHOD

INSTALLATION METHOD

Outdoor Unit

When using the anchor bolt

1.Fix the unit on a flat, rigid floor using the anchor bolt. (Anchor bolt : M10 x 4 points - separately purchased)

Installation Procedures

Anchor bolt fixing dimensions

660mm (26")

335mm (13 163 ")

1.Open the front panel, and remove the flare nut.

2.Bend the connection pipe to an appropriate length using the spring bender depending upon the installation place.

-Allowable pipe length : Maximum 25m(82ft)

-Allowable pipe drop distance : Maximum 15m(49ft)

-Make no more than ten bending points on the pipe

When the pipe length is in excess of the standard pipe length of 5m(16 83 ft), add the refrigerant (R-22) of 40g for each additional 1m(3 41 ft).

CAUTION

If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened. Therefore, the pipe length should be as short as possible (less than 15m(49ft)).

 

 

 

Outdoor unit

 

 

Indoor unit

 

 

 

15m(49ft)

Indoor unit

 

 

 

15m(49ft)

Outdoor unit

Less than

 

 

 

Less than

 

 

 

E-28

Page 28
Image 28
Samsung UPC3240C Installation Method, Installation Procedures, When using the anchor bolt, Anchor bolt fixing dimensions