Samsung UPC3240C, APC3240C installation manual Air Purge, Outdoor Unit, Pump

Models: APC3240C UPC3240C

1 36
Download 36 pages 52.33 Kb
Page 32
Image 32
AIR PURGE

AIR PURGE

The air in the indoor unit and in the pipe must be purged. If air remains in the refrigeration pipes, it will affect the compressor, reduce to cooling capacity and could lead to a malfunction.

Use Vacuum Pump as shown at the figure.

1.Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.

2.Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port as shown at the figure.

3.Open the valve of the low pressure side of manifold gauge counter-clockwise.

4.Purge the air from the system using vacuum pump for about 10 minutes.

-Close the valve of the low pressure side of manifold gauge clockwise.

-Make sure that pressure gauge show -0.1MPa(-76cmHg) after about 10 minutes. This procedure is very important in order to avoid gas leak.

-Turn off the vacuum pump.

-Remove the hose of the low pressure side of manifold gauge.

5.Set valve cork of both liquid side and gas side of packed valve to the open position.

6.Mount the valve stem nuts and the service port cap to the valve, and tighten them at the torque of 18N•m with a torque wrench.

7.Check for gas leakage.

-At this time, especially check for gas leakage from the 3-way valve’s stem nuts, and from the service port cap.

OUTDOOR UNIT

 

 

 

Gas side

 

 

Indoor unit

 

 

 

Liquid side

 

 

 

 

 

D

C

A

 

 

 

B

 

 

 

 

 

Liquid side

Gas side

Flare nut

Vacuum

3-way

3-way

 

Valve cock

Pump

valve

valve

 

B

A

Cap

 

Needle valve cap

 

 

Outdoor unit

 

 

 

E-32

 

 

 

Page 32
Image 32
Samsung UPC3240C, APC3240C installation manual Air Purge, Outdoor Unit, Pump