■Basic Function of the Service Valves

Basic Function of the Service Valves

The basic function of the service valves are given in Table 7 below.

Table 7

Action

Narrow Tube Service

Wide Tube Service

Valve (2-Way)

Valve (3-Way)

 

 

CLOSED

O-ring

Valve cap

 

 

 

Stem

Shipping

Fully OPEN

Operating and test running

the air conditioner

Fully OPEN

 

Measuring pressure

*

and gas charging

 

CLOSED

 

Air purging with

*

a vacuum pump

 

* The service port on the wide tube service

Service valve

valve uses a Schrader core valve to access

Hose with push-pin

the refrigerant system. Therefore, be sure to

 

use a hose connector which has a push-pin

 

inside. (Fig. 55)

 

PUSH

Pump Down

Pump down means collecting all refrigerant gas in the system back into the outdoor unit without losing any of the gas. Pump down is used when the unit is to be moved or before servicing the refrigerant circuit.

Pump Down Procedure

Be sure to carry out pump down with the unit in cooling mode.

(1)Connect the Lo side charging hose of the manifold valve to the service port on the wide tube service valve.

(2)Using a hex wrench, turn the narrow tube service

Fig. 55

valve clockwise all the way to close the service valve. (Be sure to confirm that the wide tube ser- vice valve is fully open.)

(3)Press the operation button and start cooling opera- tion.

(4)When the low pressure gauge reading falls to 1 to 0.5 kg/cm2 (14.2 to 7.1 PSI), fully close the wide tube valve stem with a standard screwdriver. Then quickly stop the unit.

(5)Disconnect all gauges and hoses, and replace the bonnets and the valve caps as they were before.

21

Page 21
Image 21
Sanyo CH0951, CH1251 installation instructions Basic Function of the Service Valves, Pump Down Procedure