1-6. Additional Materials Required for Installation

1.Refrigeration (armored) tape

2.Insulated staples or clamps for connecting wire (See local codes)

3.Putty

4.Refrigeration lubricant

5.Clamps or saddles to secure refrigerant tubing

Indoor unit

Drain hose

2. Installation Site Selection

2-1. Indoor Unit

To prevent abnormal heat genera-

WARNING

tion and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surround- ing the air conditioner in a way that may block air flow.

2" (5 cm) min. *6" (15 cm) min.

Outside drainage

Fig. 1

2" (5 cm) min.

 

*6" (15 cm) min.

2" (5 cm) min.

 

*6" (15 cm) min.

*KHS1852 only

Front View

AVOID:

direct sunlight.

nearby heat sources that may affect performance of the unit.

areas where leakage of flammable gas may be expected.

places where large amount of oil mist exist.

DO:

 

Fig. 2

INDOOR

Tubing length (L)

UNIT

 

Elevation

OUTDOOR

difference (H)

UNIT

 

select an appropriate position from which every corner of

the room can be uniformly cooled. (High on a wall is best.)

select a location that will hold the weight of the unit.

select a location where tubing and drain hose have the

shortest run to the outside. (Fig. 1)

Fig. 3a

CAUTION

Indoor unit

Wall

allow room for operation and maintenance as well as unre-

stricted air flow around the unit. (Fig. 2)

install the unit within the maximum elevation difference (H)

above the outdoor unit and within a total tubing length (L)

from the outdoor unit as detailed in Table 3 and Fig. 3a.

Table 3

For stable operation of the air conditioner, do not install wall-mounted type indoor units under 5 ft. (1.5 m) from floor level.

Fig. 3b

Minimum height from floor level 5 ft. (1.5 m)

Floor level

Max. Allowable Tubing

Limit of Tubing

Limit of Elevation

Required Amount of

 

Length at Shipment

Length (L)

Difference (H)

Additional Refrigerant

Model

(ft.)

(ft.)

(ft.)

(oz./ft.)*

 

 

 

 

 

 

25

50

23

a) 0.16

9,000 BTU

 

 

 

 

 

25

65

23

b) 0.27

12,000/18,000 BTU

 

 

 

 

 

*If total tubing length becomes a) 25 to 50 ft. (max.), b) 25 to 65 ft. (max.) charge additional refrigerant (R22) by a) 0.16 oz./ft., b) 0.27 oz./ft. No additional compressor oil is necessary.

4

Page 4