To unmount indoor unit

To unmount indoor unit

Press the 2 marks on the lower part of the indoor unit and unlatch the tabs. Then lift the indoor unit and unmount. (Fig. 38)

3-10. Drain Hose

a)The drain hose should be slanted downward to the outdoors. (Fig. 39)

b)Never form a trap in the course of the hose.

c)If the drain hose will run in the room, insulate the hose with insulation* so that chilled condensation will not damage furniture or floors. (Fig. 40)

*Foamed polyethylene or its equivalent is recom- mended.

WARNING Do not supply power to the unit or operate it until all tubing and wiring to the outside unit are completed.

Risk of Electric Shock

Push

Fig. 38

 

Slant

Indoor

Drain

unit

hose

 

Fig. 39

Condensation

Insulation material (locally purchased) must be used.

Fig. 40