Hole for ceiling panel hook

3-6-3. Wiring the Ceiling Panel and the Indicator

 

(1)

Remove the 2 screws from the control box cover, then open

Drain pipe side

 

 

the cover. Be careful that the cover does not fall.

 

(2)

Connect the 5P FLAP wiring connector from the ceiling

Control box

 

panel to the connector on the control PCB in the control box.

 

 

(Fig. 6-21)

Refrigerant tube side

 

 

(3)

Connect the 7P IND and 4P RC wiring connector from the

Indicator cover

 

indicator to the connectors on the control PCB in the control

 

Power box

 

box. (Fig. 6-21)

As to how to attach the indicator cover, refer to Fig.6-23.

(4) Be sure to use the clamps to fasten the connector wires in

place. (Fig. 6-21)

 

Fig. 6-22

 

 

 

 

 

 

 

 

(5) Tighten the 2 cover screws to

Ceiling panel

Indoor unit

7P IND and 4P RC

close the cover.

5P FLAP wiring connector

Indicator

 

wiring connector

 

 

 

Check that the wiring

Clamps

 

 

 

 

connectors are not caught

 

 

 

 

4P

between the electrical

 

 

 

FLAP

component box and the cover.

 

 

5P

RCIND

 

 

 

 

 

 

 

 

 

If the indicator connector is

 

5P FLAP

 

 

7P

not securely connected,

 

 

 

 

wiring connector

 

 

the remote controller

 

 

 

 

 

signal will not be

 

 

 

 

 

received.

 

 

 

 

 

If the connectors are not connected, the auto flap will not operate. Be sure

to connect them securely.

Indicator

7P IND and 4P RC wiring connector

Control box

 

 

 

 

 

* Pass the wiring connectors through the clamps to fasten them in place, as shown in the figure.

Fig. 6-21

3-6-4. How to Attach the Corner Cover and Air-Intake Grille

A. Attaching the corner cover

(1) Check that the safety strap from the corner cover is fas- tened to the ceiling panel pin, as shown in the figure. (Fig. 6-23)

(2) Use the supplied screws to attach the corner cover to the ceiling panel.

B. Attaching the air-intake grille

To install the air-intake grille, follow the steps for 3-6-1. Before Installing the Ceiling Panel in the reverse order. By rotating the air-intake grille, it is possible to attach the grille onto the ceiling panel

from any of 4 directions. (Fig. 6-25)

Pin

Place the corner cover so that the 3 tabs fit into the holes in the ceiling panel.

Then fasten it in place with the supplied screws.

Fig. 6-23

* The grille can be installed

When attaching the air-intake grille, be careful that the flap and the indicator wiring do

not become caught.

Be sure to attach the safety cord that prevents the air-intake grille from dropping off to the ceiling panel unit as shown

in Fig. 6-24.

Hook that prevents the grille from dropping

Fig. 6-24

with these hinges facing in any of 4 directions.

Can be installed rotated 90

Fig. 6-25

10

Page 81
Image 81
Sanyo XMS1272, XMS0972 service manual Wiring the Ceiling Panel and the Indicator, Attaching the air-intake grille

XMS1272, XMS0972 specifications

The Sanyo XMS0972 and XMS1272 are remarkable air conditioning units that blend efficiency with cutting-edge technology. Designed for residential and commercial spaces, these models promise comfort while optimizing energy consumption.

One of the standout features of both the XMS0972 and XMS1272 is their advanced inverter technology. This feature allows the units to adjust their cooling capacity based on the room's ambient temperature. As a result, the air conditioners can maintain a consistent temperature without the frequent on/off cycles associated with traditional units. This not only ensures a more stable climate but also significantly reduces energy consumption, making them eco-friendly options.

Another significant characteristic is the Quiet Operation mode. Both models are engineered with noise reduction technology, providing a tranquil environment for users. This is particularly beneficial for bedrooms, offices, or libraries where noise levels can be a concern. The XMS models operate at a whisper-quiet level, allowing users to focus on their tasks or enjoy a peaceful night's sleep without disruption.

The Sanyo XMS0972 and XMS1272 also feature a user-friendly digital interface. With an intuitive remote control and an easy-to-read display, setting your desired temperature or switching modes has never been easier. Moreover, the smart diagnostic capability allows for quick troubleshooting, helping to identify any issues to ensure peak performance throughout their lifespan.

Both models are equipped with a 24-hour timer, adding convenience for users who wish to come home to a pre-cooled or heated environment. This feature enhances comfort and saves energy when the unit is not in use.

In terms of design, the Sanyo XMS units boast a sleek and modern aesthetic that seamlessly integrates into various interior styles. Their compact size allows for flexible installation options, making them suitable for various living and working spaces.

The XMS line also emphasizes air purification, incorporating advanced filters that capture dust, allergens, and other pollutants. This results in not just temperature control but also improved air quality, contributing to a healthier living environment.

In conclusion, the Sanyo XMS0972 and XMS1272 air conditioning units stand out for their energy efficiency, quiet operation, user-friendly features, and air purification capabilities. These characteristics make them an ideal choice for individuals and businesses looking for reliable and sophisticated climate control solutions.