(3) Serial Communication Error Identification Procedure

If the lamps on the main body show the following conditions after the completion of self-diagnostics, a communication error between the indoor unit and outdoor unit might be considered.

In such a case, identify the breakdown section by using the following procedure.

NOTE Refer to "Method of Self-Diagnostics" for the self-diagnostics procedure.

Lamp Operation Timer

Condition

E01

E12

< Before the Operation >

High Power

: Off

: Blinking

: Illuminated

Warning

For terminal strip short circuit work or inter-unit wiring removal, turn off the power to avoid an electric shock.

Release the terminal strip short circuit after the completion of self-diagnostics.

Caution

Do not perform the short-circuit work between any other terminals except for specified ones on the specified terminal strip. If such work is performed between the incorrect terminals, the unit might be broken.

Prohibit

< Convenient Tool for Short-Circuit Work ( for example ) >

Cable

Alligator Clip

Alligator Clip

 

< Check Items before Troubleshooting Serial Communication Start >

After confirming that the following errors do not exist, start the "Troubleshooting Serial Communication" in "Condition: E01 and E12".

1.

Mis -wiring (inter-unit cable, etc.)

6.

Reactor failure (defective insulation, etc.)

2.

AC power failure

7.

High-Pressure Switch failure

3.

Blown fuse

8.

Overload Relay failure

4.

Power Relay failure

9.

Magnetic Coil failure (defective insulation, short-circuit, etc.)

5.

Outdoor Fan Motor failure (defective insulation, etc.)

10. Compressor failure (defective insulation, etc.)

(3-1) Condition: E01

Troubleshooting Serial Communication

Is the voltage of about DC12V

or more given between the terminals

2 and 3 on the outdoor unit terminal strip

(Serial Communication Line) ?

(Fig. 1)

Yes

A

( Continued to the next page A. )

 

 

-

+

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

1

 

2

 

3

4

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

4

 

5

 

6

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

 

 

 

 

 

 

 

 

1

 

2

 

3

 

 

 

 

 

 

 

 

V

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1

 

 

 

 

 

 

 

 

 

 

Fig. 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

1. Turn OFF the power and wait until the power lamp (LED)

 

of the outdoor unit controller is turned OFF.

 

 

 

2. Disconnect the cable from the terminal 3 on the indoor unit

 

 

 

 

 

 

terminal strip.

 

 

 

(Fig. 2)

 

 

 

 

 

 

 

 

 

 

3. Turn ON the power.

 

 

 

 

 

 

 

 

 

 

B

( Continued to the next page B. )

34

Page 34
Image 34
Sanyo XMS0972, XMS1272 Serial Communication Error Identification Procedure, Before the Operation, Off Blinking Illuminated

XMS1272, XMS0972 specifications

The Sanyo XMS0972 and XMS1272 are remarkable air conditioning units that blend efficiency with cutting-edge technology. Designed for residential and commercial spaces, these models promise comfort while optimizing energy consumption.

One of the standout features of both the XMS0972 and XMS1272 is their advanced inverter technology. This feature allows the units to adjust their cooling capacity based on the room's ambient temperature. As a result, the air conditioners can maintain a consistent temperature without the frequent on/off cycles associated with traditional units. This not only ensures a more stable climate but also significantly reduces energy consumption, making them eco-friendly options.

Another significant characteristic is the Quiet Operation mode. Both models are engineered with noise reduction technology, providing a tranquil environment for users. This is particularly beneficial for bedrooms, offices, or libraries where noise levels can be a concern. The XMS models operate at a whisper-quiet level, allowing users to focus on their tasks or enjoy a peaceful night's sleep without disruption.

The Sanyo XMS0972 and XMS1272 also feature a user-friendly digital interface. With an intuitive remote control and an easy-to-read display, setting your desired temperature or switching modes has never been easier. Moreover, the smart diagnostic capability allows for quick troubleshooting, helping to identify any issues to ensure peak performance throughout their lifespan.

Both models are equipped with a 24-hour timer, adding convenience for users who wish to come home to a pre-cooled or heated environment. This feature enhances comfort and saves energy when the unit is not in use.

In terms of design, the Sanyo XMS units boast a sleek and modern aesthetic that seamlessly integrates into various interior styles. Their compact size allows for flexible installation options, making them suitable for various living and working spaces.

The XMS line also emphasizes air purification, incorporating advanced filters that capture dust, allergens, and other pollutants. This results in not just temperature control but also improved air quality, contributing to a healthier living environment.

In conclusion, the Sanyo XMS0972 and XMS1272 air conditioning units stand out for their energy efficiency, quiet operation, user-friendly features, and air purification capabilities. These characteristics make them an ideal choice for individuals and businesses looking for reliable and sophisticated climate control solutions.