Schneider Electric ACECFR40101SE Service access, 121948, 243896, Wall Or Other Obstruction

Models: ACECFR40201SE ACECFR20201SE ACECFR40101SE ACECFR40200SE ACECFR20200SE ACECFR20101SE

1 32
Download 32 pages 61.48 Kb
Page 15
Image 15
Service access

Service access

Install a service platform (not supplied) to facilitate maintenance activities. Regular maintenance activities require a of minimum 1219 mm (48 in.) clearance on all sides to remove, maneuver, and install Modules and components.

1219 (48)

1219 (48)

1219 (48)

1219 (48)

na3526a

NOTE: Consider local soil conditions, codes, and loading when determining appropriate support footings.

To prevent short cycling of outdoor air, each EcoBreeze Frame must have a minimum of 1219 mm (48 in.) clearance on each side, totaling 2438 mm (96 in.) between Frames, and 1219 mm (48 in.) at the end of the Frame.

1219 (48) 1219 (48)1219 (48)

1219 (48)

2438 (96)

1219 (48)

 

WALL OR OTHER OBSTRUCTION

na3677a

 

* Dimensions are shown in millimeters with inches in parentheses.

EcoBreeze System Installation

11

Page 15
Image 15