AIR GAP

NOTE: Separate the drain line from the EcoBreeze Frame and the external drain line by a

50 mm (2 in.) air gap in order to prevent back up of contaminated water into the cooling system.

AIR GAP

na3564a

NOTE: Pitch the external drain piping at a minimum of 25 mm (1 in.) per 3048 mm (10 ft) towards the wastewater drain.