Schneider Electric ACECFR40201SE, ACECFR20101SE, ACECFR20200SE Building Management System, 1MOD

Models: ACECFR40201SE ACECFR20201SE ACECFR40101SE ACECFR40200SE ACECFR20200SE ACECFR20101SE

1 32
Download 32 pages 61.48 Kb
Page 29
Image 29
Building Management System

Building Management System

The Modbus interface allows the EcoBreeze System to communicate with a building management system (BMS).

The Modbus connection is available in two locations on the Modbus hub:

RJ-45 In port

3-wire on terminal block

For an RJ-45 connection, wire as follows:

Pin 4

D(A)

Pin 5

D(B)

Pin 8

Ground

For a direct 3-wire connection, connect to the corresponding contacts on the green terminal block on the side of the Modbus hub. No connection is necessary to the 0V contact.

 

WIRING CONTACTS

 

DDC PANEL

 

 

ENCLOSURE

 

FOR DIRECT 3-WIRE

RJ-45 IN PORT

 

 

 

CONNECTION

 

 

 

 

1MOD

 

 

D(B)

 

 

 

D(A)

 

 

 

1MOD

 

 

na3660a

0 V

 

 

 

 

 

EcoBreeze System Installation

25

Page 29
Image 29
Schneider Electric ACECFR40201SE, ACECFR20101SE, ACECFR20200SE, ACECFR40200SE, ACECFR40101SE Building Management System, 1MOD