PowerLogicTM EM4800 Series

930-110-01-B.00

Installation

04/2011

 

 

For a 208Y/120V three-phase wye panel with the 120V variant of the meter:

Connect meter terminal A to the voltage disconnect phase A (red wire)

Connect meter terminal B to the voltage disconnect phase B (black wire)

Connect meter terminal C to the voltage disconnect phase C (blue wire)

Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)

Connect earth wire to earth post using lug provided

Install power supply shorting jumpers (see Figure 7)

Figure 7: PowerLogic EM4800 meter 208Y/120V three-phase wye service connection

2

3

4

5

1

8

7

9

6

Legend:

1BX cable

2 Earth

3 Phase C (blue)

4 Phase B (black)

5 Shorting jumper

6 Sense voltage terminal block (J3)

7 Neutral (white)

8 Phase A (red)

9 0.75-inch (1.9-cm) strain relief