To connect the 5A CT to the converter on the PowerLogic EM4880, follow
these steps:
1. Connect the X1 lead of the 5A CT to the shorting device.
2. Connect the X2 lead of the 5A CT to the shorting device.
3. Connect the X1 lead (red) from the 5A side of the converter to the CT
X1 lead on the shorting device.
4. Connect the X2 lead (black) from the 5A side of the converter to the CT
X2 lead on the shorting device.
5. Connect the X1 lead (white) from the 80mA side of the converter to the
X1 lead within the 25 pair cable for the selected meter point ID listed in
Table 2.
6. Connect the X2 lead (black) from the 80mA side of the converter to the
X2 lead within the 25 pair cable for the selected meter point ID listed in
Table 2
Figure 14 shows a 5A CT connected to the converter.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on or
inside the equipment.
Always use a properly rated voltage sensing device to confirm the
power is off.
NEVER open circuit a CT; use the shorting block to short circuit the
leads of the CT before removing the connection from the meter.
Do not crimp the insulation when making the wire connections.
Failure to followthese instructions will result in death or
serious injury.