930-110-01-B.00 PowerLogicTM EM4800 Series
04/2011 Installation
© 201 Schneider Electric All Rights Reserved 11
Installing Potential Transformers for
Three-Phase Service Greater Than 277V Potential transformers are required when metering services greater than the
rated voltage input of the meter. Potential transformers are used to reduce
the line-to-neutral voltage of the service to 120V. The accuracy class should
be 0.3% or better, with a burden rating of 30VA.
For applications in Canada, Measurement Canada approved potential
transformers are required. Measurement Canada requires an accuracy class
of 0.3% or better, with a 150VA rating.
NOTE: Potential transformer burden depends on the control voltage
source. If control voltage is provided separately (not derived from the
metered voltage), then lower transformer burden may be acceptable.
Contact your local Schneider Electric representative for details.
Mount the potential transformer enclosure between the supply voltage and
the PowerLogic meters as shown in Figure 5. Transformer configuration
must be Y||Y (wye-wye).
In Figure 5, the meter is powered from the potential transformers that are fed
from a breaker within the 600Y/347V panel. The CT cable is connected to the
shorting enclosure before connecting to the CTs in the panel.