Analog Inputs (Meter Ordering Option): AI1 to AI4

 

 

 

 

 

 

 

 

 

 

 

 

PowerLogic ION7550 / ION7650 Installation Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Inputs (Meter Ordering Option): AI1 to AI4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

Captured wire connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wire

1.3 to 0.1 mm2 (16 to 28 AWG)

 

 

 

AI3

 

 

 

 

Signal Type

DC current

+ -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Available Options

0 to 20 mA (scalable 4-20 mA) or 0 to 1 mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Impedance

24 Ω (0-20 mA option) or 475 Ω (0-1 mA option)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Accuracy

+/– 0.3% of full scale

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Update Rate

1 s

 

AI4 AI3 AI2

AI1

 

 

Isolation to Ground

750 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Isolation Impedance

max 400 kΩ (channel/channel)

 

 

 

 

 

 

 

 

 

 

 

 

 

mV

Thermocoupler

Voltage-to-

Current

Transducer

mA

Meter

Example

 

 

+

 

application:

 

AI1

temperature

 

-

sensing

 

 

Analog Outputs (Meter Ordering Option): AO1 to AO4 NOTE

Do not connect the analog inputs of the I/O card to the analog outputs on the same I/O card.

Analog Outputs (Meter Ordering Option): AO1 to AO4

AO3

OUT COM

AO4

A03

A02

AO1

Type

Captured wire connector

 

 

Wire

1.3 to 0.1 mm2 (16 to 28 AWG)

Signal Type

DC current

 

 

Available Options

0 to 20 mA (scalable 4-20 mA) or -1 to 1 mA

(scalable 0-1 mA)

 

 

 

Driving Capability

500 Ω (0-20 mA option) or 10 kΩ (-1 to 1 mA

option)

 

 

 

Accuracy

+/– 0.30% of full scale

 

 

Update Rate

½ cycle or 1 s

Latency

min. 1 cycle for measurement + ½ cycle for ION

+ 1 s delay for hardware

 

 

 

Isolation to Ground

750 V

 

 

Analog + Meter

Meter

Manual background OUT

AO1

Manual background COM

Example application: driving an analog meter with the DC current output

Manual background NOTE

Do not connect the analog outputs of the I/O card to the analog inputs on the same I/O card.

© 2007 Schneider Electric. All rights reserved.

11

Page 11
Image 11