Schneider Electric ION7650 Mount the Meter, Wire the Ground Terminal, Integrated Display Model

Models: ION7550 ION7650

1 28
Download 28 pages 3.61 Kb
Page 8
Image 8
Step 1: Mount the Meter

PowerLogic ION7550 / ION7650 Installation Guide

Step 1: Mount the Meter

Environmental Specifications

Mounting Location

Indoor use

 

 

 

-20 to +70ºC (-4 to +158ºF) Standard Power Supply

Operating Range

-20 to +50ºC (-4 to +122ºF) Low Voltage DC Power Supply

 

No formation of ice

 

 

Display Operating Range

-20 to +70ºC (-4 to +158ºF)

 

 

Storage Range

-40 to +85ºC (-40 to +185ºF)

 

 

Relative Humidity Range

5 to 95% non-condensing

Meter Battery Considerations

The meter’s battery life expectancy depends on both temperature and the amount of time the meter is without power. For typical installations, the battery should last 20 years or more. If the meter is not powered, the battery will last a minimum of 7 years at room temperature.

Integrated Display Model

1.Fit the meter into the DIN standard 192 cutout (186 mm by 186 mm).

2.Slide the four brackets into their slots on the back of the meter and secure using the four Phillips head screws. Do not overtighten.

Screw

DIN 192

Cutout

Bracket

Step 2: Wire the Ground Terminal

Connect the Environmental Specifications terminal to a good earth ground with a 2.1 mm2 (14 AWG) wire. Ensure that the terminal nut is tightened down securely onto the ground wire. Do not use metal door hinges as a grounding point.