PowerLogic ION7550 / ION7650 Installation Guide
Front Panel Setup Menu Settings
Menu
BASIC SETUP
The following table lists all settings that can be configured via the front panel.
Setting | Description | Range (Values) | Default | |
VOLTS MODE | The power system’s configuration – | |||
WYE, DELTA, etc. | SINGLE, DEMO | |||
|
| |||
|
|
|
| |
PT PRIMARY | The Potential Transformer’s primary | 1 to 999,999.99 | 120.00 | |
| winding voltage rating |
|
| |
PT SECONDARY | The Potential Transformer’s | 1 to 999,999.99 | 120.00 | |
secondary winding voltage rating | ||||
|
|
| ||
|
|
|
| |
CT PRIMARY | The Current Transformer’s primary | 1 to 999,999.99 | 5.00 | |
winding current rating | ||||
|
|
| ||
|
|
|
| |
CT SECONDARY | The Current Transformer’s | 1 to 999,999.99 | 5.00 | |
| secondary winding current rating |
|
| |
V4 PRIMARY | The Potential Transformer’s primary | 1 to 999,999.99 | 120.00 | |
| winding voltage rating on V4 |
|
| |
| The Potential Transformer’s |
|
| |
V4 SECONDARY | secondary winding voltage rating | 1 to 999,999.99 | 120.00 | |
| on V4 |
|
| |
|
|
|
| |
I4 PRIMARY | The Current Transformer’s primary | 1 to 999,999.99 | 5.00 | |
winding current rating on I4 | ||||
|
|
| ||
|
|
|
| |
| The Current Transformer’s |
|
| |
I4 SECONDARY | secondary winding current rating | 1 to 999,999.99 | 5.00 | |
| on I4 |
|
| |
|
|
|
| |
I5 PRIMARY | The Current Transformer’s primary | 1 to 999,999.99 | 5.00 | |
winding current rating on I5 | ||||
|
|
| ||
|
|
|
| |
| The Current Transformer’s |
|
| |
I5 SECONDARY | secondary winding current rating | 1 to 999,999.99 | 5.00 | |
| on I5 |
|
| |
|
|
|
| |
V NOMINAL | The V1, V2 and V3 nominal voltage | 1.000 to 999,999.000 | 120.00 | |
| used for harmonics calculations |
|
| |
V4 NOMINAL | The V4 nominal voltage used for | 1.000 to 999,999.000 | 120.00 | |
harmonics calculations | ||||
|
|
| ||
|
|
|
| |
Va POLARITY | The polarity of the Potential | Normal or Inverted | Normal | |
Transformer on Va | ||||
|
|
| ||
|
|
|
| |
Vb POLARITY | The polarity of the Potential | Normal or Inverted | Normal | |
Transformer on Vb | ||||
|
|
| ||
|
|
|
| |
Vc POLARITY | The polarity of the Potential | Normal or Inverted | Normal | |
Transformer on Vc | ||||
|
|
| ||
|
|
|
| |
V4 POLARITY | The polarity of the Potential | Normal or Inverted | Normal | |
Transformer on V4 | ||||
|
|
| ||
|
|
|
| |
Ia POLARITY | The polarity of the Current | Normal or Inverted | Normal | |
Transformer on Ia | ||||
|
|
| ||
|
|
|
| |
Ib POLARITY | The polarity of the Current | Normal or Inverted | Normal | |
Transformer on Ib | ||||
|
|
| ||
|
|
|
| |
Ic POLARITY | The polarity of the Current | Normal or Inverted | Normal | |
Transformer on Ic | ||||
|
|
| ||
|
|
|
| |
I4 POLARITY | The polarity of the Current | Normal or Inverted | Normal | |
Transformer on I4 | ||||
|
|
| ||
|
|
|
| |
I5 POLARITY | The polarity of the Current | Normal or Inverted | Normal | |
Transformer on I5 | ||||
|
|
| ||
|
|
|
| |
CURRENT PROBE | The type of current probes being | Factory Default, User Defined 1, | Factory | |
TYPE | used with the meter | or User Defined 2 | Default | |
|
|
|
|