PowerLogic ION7550 / ION7650 Installation Guide
Menu | Setting | Description | Range (Values) | Default | |
|
|
| ION, Modbus RTU, Modbus |
| |
| PROTOCOL | The communications protocol | Master, DNP V3.00, | ION | |
| GPS:Truetime/Datum,GPS: | ||||
|
|
| Arbiter, |
| |
|
|
| Factory, Ethergate, ModemGate |
| |
|
|
|
|
| |
SETUP | BAUD RATE | The data rate, in bits per second | 3001, 1200, 2400, 4800, 9600, | 19,200 | |
|
| 19200, 38400, 57600, 115200 |
| ||
| TRAN DELAY | The transmit delay in seconds | 0 to 1 | 0.010 | |
|
|
|
|
| |
COM1 | UNIT ID | Every meter on an | 1 to 9999 | From serial | |
must have a unique Unit ID number | number2 | ||||
| |||||
| SERIAL PORT | Parity and stop bits for the port | 8N1, 8N2, 8E1, 8E2, 8O1, 8O2 | 8N1 | |
|
|
|
|
| |
| MODE | Hardware mode for the port | RS232 or RS485 | RS232 | |
|
|
|
|
| |
| FLOW CONTROL | Specifies the handshake mode | RTS + DELAY or RTS/CTS | RTS + | |
| when COM1 is set to RS232 | DELAY | |||
|
|
|
|
| |
| RS485 BIAS | Turns on biasing when Mastering | ON or OFF | OFF | |
| on the | ||||
|
|
|
| ||
| PROTOCOL | The communications protocol | See COM1 protocol | ION | |
|
|
|
|
| |
| BAUD RATE | The data rate, in bits per second | 3001, 1200, 2400, 4800, 9600, | 19,200 | |
SETUP |
|
| 19200, 38400, 57600, 115200 |
| |
| TRAN DELAY | The transmit delay in seconds | 0 to 1 | 0.010 | |
|
|
|
|
| |
COM2 | UNIT ID | Every meter on an | 1 to 9999 | 101 | |
must have a unique Unit ID number | |||||
|
|
|
| ||
SERIAL PORT | Parity and stop bits for the port | 8N1, 8N2, 8E1, 8E2, 8O1, 8O2 | 8N1 | ||
|
|
|
|
| |
| RS485 BIAS | Turns on biasing when Mastering | ON or OFF | OFF | |
| on the | ||||
|
|
|
| ||
|
|
| ION, Modbus RTU, Modbus |
| |
|
|
| Master, DNP V3.00, |
| |
| PROTOCOL | The communications protocol | GPS:Truetime/Datum,GPS: | ION | |
|
|
| Arbiter, |
| |
|
|
| Factory |
| |
SETUP |
|
|
|
| |
BAUD RATE | The data rate, in bits per second | 3001, 1200, 2400, 4800, 9600, | 19,200 | ||
|
|
| 19200, 38400, 57600, 115200 |
| |
COM3 | TRAN DELAY | The transmit delay in seconds | 0 to 1 | 0.010 | |
|
|
|
| ||
| UNIT ID | Every meter on an | 1 to 9999 | 102 | |
|
| must have a unique Unit ID number |
|
| |
| ANSWER HR | The number of rings during defined | 0 to 255 | 1 | |
| RINGS | answer hours |
|
| |
| The number of rings during defined | 0 to 255 | 5 | ||
| HR RINGS |
|
| ||
| PROTOCOL | The communications protocol | ION, Modbus RTU, DNP V3.00, | ION | |
SETUP |
|
| Factory |
| |
| BAUD RATE | The data rate, in bits per second | 1200, 2400, 4800, 9600, | 9600 | |
| 19200 | ||||
|
|
|
| ||
|
|
|
|
| |
COM4 | TRAN DELAY | The transmit delay in seconds | 0 to 1 | 0.010 | |
|
|
|
| ||
| UNIT ID | Every meter on an | 1 to 9999 | 103 | |
|
| must have a unique Unit ID number |
|
| |
| SERIAL PORT | Parity and stop bits for the port | 8N1, 8N2, 8E1, 8E2, 8O1, 8O2 | 8N1 | |
|
|
|
|
|
© 2007 Schneider Electric. All rights reserved. | 21 |