Schneider Electric ION7550, ION7650 manual COM1, Setup

Models: ION7550 ION7650

1 28
Download 28 pages 3.61 Kb
Page 21
Image 21
COM1

PowerLogic ION7550 / ION7650 Installation Guide

Menu

Setting

Description

Range (Values)

Default

 

 

 

ION, Modbus RTU, Modbus

 

 

PROTOCOL

The communications protocol

Master, DNP V3.00,

ION

 

GPS:Truetime/Datum,GPS:

 

 

 

Arbiter, GPS:Arbiter-Vorne,

 

 

 

 

Factory, Ethergate, ModemGate

 

 

 

 

 

 

SETUP

BAUD RATE

The data rate, in bits per second

3001, 1200, 2400, 4800, 9600,

19,200

 

 

19200, 38400, 57600, 115200

 

 

TRAN DELAY

The transmit delay in seconds

0 to 1

0.010

 

 

 

 

 

COM1

UNIT ID

Every meter on an RS-485 network

1 to 9999

From serial

must have a unique Unit ID number

number2

 

 

SERIAL PORT

Parity and stop bits for the port

8N1, 8N2, 8E1, 8E2, 8O1, 8O2

8N1

 

 

 

 

 

 

MODE

Hardware mode for the port

RS232 or RS485

RS232

 

 

 

 

 

 

FLOW CONTROL

Specifies the handshake mode

RTS + DELAY or RTS/CTS

RTS +

 

when COM1 is set to RS232

DELAY

 

 

 

 

 

 

RS485 BIAS

Turns on biasing when Mastering

ON or OFF

OFF

 

on the RS-485 bus

 

 

 

 

 

PROTOCOL

The communications protocol

See COM1 protocol

ION

 

 

 

 

 

 

BAUD RATE

The data rate, in bits per second

3001, 1200, 2400, 4800, 9600,

19,200

SETUP

 

 

19200, 38400, 57600, 115200

 

 

TRAN DELAY

The transmit delay in seconds

0 to 1

0.010

 

 

 

 

 

COM2

UNIT ID

Every meter on an RS-485 network

1 to 9999

101

must have a unique Unit ID number

 

 

 

 

SERIAL PORT

Parity and stop bits for the port

8N1, 8N2, 8E1, 8E2, 8O1, 8O2

8N1

 

 

 

 

 

 

RS485 BIAS

Turns on biasing when Mastering

ON or OFF

OFF

 

on the RS-485 bus

 

 

 

 

 

 

 

ION, Modbus RTU, Modbus

 

 

 

 

Master, DNP V3.00,

 

 

PROTOCOL

The communications protocol

GPS:Truetime/Datum,GPS:

ION

 

 

 

Arbiter, GPS:Arbiter-Vorne,

 

 

 

 

Factory

 

SETUP

 

 

 

 

BAUD RATE

The data rate, in bits per second

3001, 1200, 2400, 4800, 9600,

19,200

 

 

 

19200, 38400, 57600, 115200

 

COM3

TRAN DELAY

The transmit delay in seconds

0 to 1

0.010

 

 

 

 

 

UNIT ID

Every meter on an RS-485 network

1 to 9999

102

 

 

must have a unique Unit ID number

 

 

 

ANSWER HR

The number of rings during defined

0 to 255

1

 

RINGS

answer hours

 

 

 

NON-ANSWER

The number of rings during defined

0 to 255

5

 

HR RINGS

non-answer hours

 

 

 

PROTOCOL

The communications protocol

ION, Modbus RTU, DNP V3.00,

ION

SETUP

 

 

Factory

 

 

BAUD RATE

The data rate, in bits per second

1200, 2400, 4800, 9600,

9600

 

19200

 

 

 

 

 

 

 

 

 

COM4

TRAN DELAY

The transmit delay in seconds

0 to 1

0.010

 

 

 

 

 

UNIT ID

Every meter on an RS-485 network

1 to 9999

103

 

 

must have a unique Unit ID number

 

 

 

SERIAL PORT

Parity and stop bits for the port

8N1, 8N2, 8E1, 8E2, 8O1, 8O2

8N1

 

 

 

 

 

© 2007 Schneider Electric. All rights reserved.

21

Page 21
Image 21
Schneider Electric ION7550, ION7650 manual COM1, Setup