PowerLogic ION7550 / ION7650 Installation Guide
Step 6: Wire the Power Supply
|
|
|
|
|
|
|
|
|
|
|
|
| Specification | Standard Power Supply | Low Voltage DC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Type | Captured wire connector |
|
| G L + N | _ |
| Wire | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| Rated Inputs | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| or |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Dielectric Withstand | 2500 VAC RMS at 60 Hz for 60s |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Burden | 35 VA max. (15 VA typical) | 18 W max. (12 W typical) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 100 ms (6 cycles at 60 Hz) min. | None |
Step 7: Power Up the Meter
1.Ensure the ground wire is securely connected on both ends.
2.Ensure the meter’s power supply voltage is within the allowed range.
3.Power up the meter.
Step 8: Set Up the Meter Using the Front Panel
The following Setup screens are available for meter configuration via the front panel:
BASIC SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
COM4 SETUP
NETWORK SETUP
PQ SETUP
FORMAT SETUP
DISPLAY SETUP
TIME SETUP
SECURITY SETUP
METER RESETS
Use the PROG/SELECT, ESC, softkeys and arrow buttons to configure settings. The following example shows Volts Mode setup using the meter front panel.
Press PROG/SELECT to enter Setup Mode from Display Mode.
Press
Press
Press
Use arrow buttons to move up and down in list. Press PROG/SELECT to select Basic Setup.
Press
Press
| Press |
Use arrow buttons to |
|
move up and down in | Press Mode softkey. |
list. Press PROG/SELECT | Use arrow buttons to |
to select PT/CT Setup. | move up and down in |
| list. Press PROG/SELECT |
| to select Delta. |