Schneider Electric ION7650 Wire Solid-Grounded Wye, 3-Element, Direct Connection, Load, Line

Models: ION7550 ION7650

1 28
Download 28 pages 3.61 Kb
Page 14
Image 14
3-Wire Solid-Grounded Wye, 3-Element, Direct Connection

PowerLogic ION7550 / ION7650 Installation Guide

3-Wire Solid-Grounded Wye, 3-Element, Direct Connection

LINE

LOAD

Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

When the common or star point of a 3-wire Wye system is grounded, the meter may be connected directly without using PTs, provided that the phase voltages are within the meter’s range.

VOLTS MODE = 4W-Wye

3-Wire Delta, 2½-Element, Direct Connection

LINE

ALOAD

B C

LOAD

Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

2A

3A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1 V2

V3 V4 Vref

 

I11

I12

I21

I22

I31

I32

I41

I42

I51

I52

 

 

 

 

 

 

 

 

 

 

 

G L / + N/-

600V L-L max. VOLTS MODE = Delta

3-Wire Delta, 2-Element 2 PTs & 2 CTs

LINE

A

LOAD

B

 

C

 

2A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I11

 

I21

 

 

I31

 

 

I41

 

I51

 

V1 V2

V3 V4 Vref

 

I12

I22

I32

 

I42

I52

 

 

 

 

 

 

 

 

 

 

 

 

Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

3A3-Wire Delta, 2½-Element, Direct Connection

G L / + N/-

Use PTs for voltages over 600 V L-L. VOLTS MODE = Delta

14

© 2007 Schneider Electric. All rights reserved.

Page 14
Image 14
Schneider Electric ION7650 Wire Solid-Grounded Wye, 3-Element, Direct Connection, Wire Delta, 2-Element 2 PTs & 2 CTs