Menu | Setting | Description | Range (Values) | Default | |
| IP ADDRESS | Sets the IP address for the meter | 000.000.000.000 to | varies3 | |
| 999.999.999.999 | ||||
|
|
|
| ||
|
|
|
|
| |
| SUBNET MASK | Used if subnetting applies to your | 000.000.000.000 to | 255.240.0.0 | |
| network | 999.999.999.999 | |||
|
|
| |||
|
|
|
|
| |
| GATEWAY | Used in multiple network | 000.000.000.000 to | 0.0.0.0 | |
SETUP | configurations | 999.999.999.999 | |||
|
| ||||
|
|
|
| ||
|
| Sets the address for the primary | 000.000.000.000 to |
| |
| DNS PRIMARY | DNS Server that is configured to | none | ||
NETWORK | 999.999.999.999 | ||||
| resolve domain names |
| |||
|
|
| |||
|
|
|
| ||
| DNS | Sets the address for the secondary | 000.000.000.000 to |
| |
| DNS Server that is configured to | none | |||
| SECONDARY | 999.999.999.999 | |||
| resolve domain names |
| |||
|
|
|
| ||
|
|
|
|
| |
| 10/100BT | Sets the | Auto, 10BT half, 10BT full, | Auto | |
| CONFIG | speed and duplexing | 100BTX half, 100BTX full | ||
|
| ||||
|
|
|
|
| |
| 100BFX CONFIG | Sets the Fiber Ethernet duplexing | Full Duplex or Half Duplex | Full Duplex | |
|
|
|
|
| |
| SNMP SERVER | Determines whether SNMP protocol | Enabled or Disabled | Disabled | |
|
| is enabled on the meter or not |
|
| |
|
| Specifies the magnitude above |
|
| |
| SWELL LIMIT | which an input must rise for a swell | 100 to 1000 | 106 | |
|
| to be recorded |
|
| |
|
|
|
|
| |
|
| Specifies the magnitude below |
|
| |
| SAG LIMIT | which an input must fall for a sag to | 0 to 100 | 88 | |
SETUP |
| be recorded |
|
| |
|
|
|
| ||
CHANGE | Specifies the amount by which an |
|
| ||
input must change during a | 0 to 100 | 10 | |||
PQ | CRITERIA | disturbance to be considered a new | |||
|
|
| |||
|
|
|
| ||
|
|
|
|
| |
| NOMINAL | Specifies the nominal voltage of the | 0 to 1,000,000 | 0 | |
| VOLTAGE4 | power system |
|
| |
| EVENT PRIORITY | Assigns a priority level to sag/swell | 0 to 255 | 200 | |
|
| events |
|
| |
| DIGIT GROUP | Specifies symbols used to delimit | 1000.0 or 1,000.0 or 1000,0 | 1000.0 | |
| thousands & decimal place holder | ||||
|
|
|
| ||
|
|
|
|
| |
| VOLTS DECIMAL | Number of decimal places | 1. to 123456789.XXX | 1.XX | |
| displayed for voltages | ||||
|
|
|
|
| |
| CURRNT | Number of decimal places | 1. to 123456789.XXX | 1.XXX | |
| DECIMAL | displayed for currents | |||
|
|
| |||
|
|
|
|
| |
| POWER DECIMAL | Number of decimal places | 1. to 123456789.XXX | 1.XXX | |
SETUP |
| displayed for power measurements |
|
| |
| MEAS SYMBOL | Specifies the convention used for | IEEE or IEC | IEEE | |
| displaying measurements | ||||
|
|
|
| ||
|
|
|
|
| |
FORMAT | PHASE LABEL | Specifies how phases are labelled | ABC, RST, XYZ, RYB, RWB, 123 | ABC | |
|
|
|
| ||
| PF SIGN | Specifies the power factor sign | IEEE or IEC | IEEE | |
| convention used | ||||
|
|
|
| ||
|
|
|
|
| |
| PF SYMBOL | Sets how power factor is labelled | LD/LG, | LD/LG | |
| (LD = leading/LG = lagging) | ||||
|
|
|
| ||
|
|
|
|
| |
| DATE FORMAT | Specifies how dates are displayed | MM/DD/YYYY, DD/MM/YYYY, | MM/DD/ | |
| YYYY/MM/DD | YYYY | |||
|
|
| |||
|
|
|
|
| |
| TIME FORMAT | Specifies whether time is displayed | 12 H or 24 H | 24 H | |
| in 12 hour or 24 hour clock format | ||||
|
|
|
|
| |
| DISPLAY DST | Specifies whether or not DST is | Yes or No | Yes | |
| displayed | ||||
|
|
|
| ||
|
|
|
|
|