Schneider Electric ION7650, ION7550 manual Menu, Setting, Description, Range Values, Default, Setup

Models: ION7550 ION7650

1 28
Download 28 pages 3.61 Kb
Page 22
Image 22
SETUP

PowerLogic ION7550 / ION7650 Installation Guide

Menu

Setting

Description

Range (Values)

Default

 

IP ADDRESS

Sets the IP address for the meter

000.000.000.000 to

varies3

 

999.999.999.999

 

 

 

 

 

 

 

 

 

 

SUBNET MASK

Used if subnetting applies to your

000.000.000.000 to

255.240.0.0

 

network

999.999.999.999

 

 

 

 

 

 

 

 

 

GATEWAY

Used in multiple network

000.000.000.000 to

0.0.0.0

SETUP

configurations

999.999.999.999

 

 

 

 

 

 

 

 

Sets the address for the primary

000.000.000.000 to

 

 

DNS PRIMARY

DNS Server that is configured to

none

NETWORK

999.999.999.999

 

resolve domain names

 

 

 

 

 

 

 

 

 

DNS

Sets the address for the secondary

000.000.000.000 to

 

 

DNS Server that is configured to

none

 

SECONDARY

999.999.999.999

 

resolve domain names

 

 

 

 

 

 

 

 

 

 

 

10/100BT

Sets the BASE-T Ethernet max. link

Auto, 10BT half, 10BT full,

Auto

 

CONFIG

speed and duplexing

100BTX half, 100BTX full

 

 

 

 

 

 

 

 

100BFX CONFIG

Sets the Fiber Ethernet duplexing

Full Duplex or Half Duplex

Full Duplex

 

 

 

 

 

 

SNMP SERVER

Determines whether SNMP protocol

Enabled or Disabled

Disabled

 

 

is enabled on the meter or not

 

 

 

 

Specifies the magnitude above

 

 

 

SWELL LIMIT

which an input must rise for a swell

100 to 1000

106

 

 

to be recorded

 

 

 

 

 

 

 

 

 

Specifies the magnitude below

 

 

 

SAG LIMIT

which an input must fall for a sag to

0 to 100

88

SETUP

 

be recorded

 

 

 

 

 

 

CHANGE

Specifies the amount by which an

 

 

input must change during a

0 to 100

10

PQ

CRITERIA

disturbance to be considered a new

 

sub-disturbance

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL

Specifies the nominal voltage of the

0 to 1,000,000

0

 

VOLTAGE4

power system

 

 

 

EVENT PRIORITY

Assigns a priority level to sag/swell

0 to 255

200

 

 

events

 

 

 

DIGIT GROUP

Specifies symbols used to delimit

1000.0 or 1,000.0 or 1000,0

1000.0

 

thousands & decimal place holder

 

 

 

 

 

 

 

 

 

 

VOLTS DECIMAL

Number of decimal places

1. to 123456789.XXX

1.XX

 

displayed for voltages

 

 

 

 

 

 

CURRNT

Number of decimal places

1. to 123456789.XXX

1.XXX

 

DECIMAL

displayed for currents

 

 

 

 

 

 

 

 

 

POWER DECIMAL

Number of decimal places

1. to 123456789.XXX

1.XXX

SETUP

 

displayed for power measurements

 

 

 

MEAS SYMBOL

Specifies the convention used for

IEEE or IEC

IEEE

 

displaying measurements

 

 

 

 

 

 

 

 

 

FORMAT

PHASE LABEL

Specifies how phases are labelled

ABC, RST, XYZ, RYB, RWB, 123

ABC

 

 

 

 

 

PF SIGN

Specifies the power factor sign

IEEE or IEC

IEEE

 

convention used

 

 

 

 

 

 

 

 

 

 

PF SYMBOL

Sets how power factor is labelled

LD/LG, +/-, CAP/IND

LD/LG

 

(LD = leading/LG = lagging)

 

 

 

 

 

 

 

 

 

 

DATE FORMAT

Specifies how dates are displayed

MM/DD/YYYY, DD/MM/YYYY,

MM/DD/

 

YYYY/MM/DD

YYYY

 

 

 

 

 

 

 

 

 

TIME FORMAT

Specifies whether time is displayed

12 H or 24 H

24 H

 

in 12 hour or 24 hour clock format

 

 

 

 

 

 

DISPLAY DST

Specifies whether or not DST is

Yes or No

Yes

 

displayed

 

 

 

 

 

 

 

 

 

22

© 2007 Schneider Electric. All rights reserved.

Page 22
Image 22
Schneider Electric ION7650, ION7550 manual Menu, Setting, Description, Range Values, Default, Setup