Schneider Electric manual S7-200 Series

Models: S7

1 22
Download 22 pages 6.45 Kb
Page 14
Image 14
S7-200 Series

SIMATIC S7 Ethernet

*7 PLC word addresses defined for integer, float, and string variables must be even-numbered. i.e., IW5 is not a valid device address for an integer variable. Must be either IW4 or IW6.

*8 16-bit and 32-bit data, High and Low, refer to data as defined in the following examples.

S7-200 Series

Device

Bit Address* 1

 

Word Address

 

bit

bit

 

 

 

 

 

Variable*2

V00000.0-V10239.7

VW00000-VW10238

 

 

 

I00000.0-I00015.7

 

IW00000-IW00014

 

 

 

 

or

 

or

 

 

 

Input*3*2

E00000.0-E00015.7*6

EW00000-EW0000014*6

 

 

 

Q00000.0-Q00015.7

QW00000-QW00014

 

 

* 2*4

or

*6

or

*6

H/L*5

H/L*5

Output

A00000.0-A00015.7

 

AW00000-AW00014

 

 

Marker

M00000.0-M00031.7

MW00000-MW00030

 

 

Timer Word*7

 

T00000-T00255

 

 

 

 

 

 

C00000-C00255

 

 

 

 

 

 

or

 

 

 

Counter Word*7

 

Z00000-Z00255*6

 

 

 

*1 Read-modify-write. When you write to one of these bit addresses, the target machine reads the entire word address, sets the defined bit, then returns the new value to the PLC. If the ladder program writes data to this word address during the bit read/write process, the resulting data may be incorrect.

*2 PLC word addresses defined for integer, float, and string variables must be even-numbered. i.e., IW5 is not a valid device address for an integer variable. Must be either IW4 or IW6.

*3 Depending on the CPU type, it may not be possible to write to addresses IW0- IW2. These addresses are reserved for onboard I/O.

*4 It is possible to write to the QW / Q device only while the PLC is in RUN mode. Outputs will be reset if the PLC is switched into stop mode.

*5 16-bit and 32-bit data, High and Low, refer to data as defined in the following examples.

*5 German variable name.

*6 These devices are read-only.

14

Page 14
Image 14
Schneider Electric manual S7-200 Series