Security Centres 808 manual Programming, Initial Power Up

Models: 808

1 22
Download 22 pages 54.06 Kb
Page 8
Image 8
Programming

Programming

808

2k2 EOL

4k7

Alarm contacts

Tamper Loop

Zone 1

CCT

Note: When wiring FSL zones, link out the anti-tamper terminals of each zone in use

on the main connnector and expander cards.

Zone 1

AT

Figure 4. Wiring Diagram for Single Alarm Contacts and Tamper Wiring

With the loop in a normal state and the alarm contacts closed (shorting out the 4K7 resistor), the total resistance of the loop is 2K2 ohms. When the alarm loop is opened and the short removed from the 4K7 resistor, the resistor is brought into the circuit and the resistance of the loop is increased to 6K9 causing the end station to detect an alarm condition. If a tamper device is opened, the loop resistance will be open circuit and the end station will detect a tamper signal.

The wiring resistance should be restricted to a maximum of 100 ohms. The recommended maximum cable distance per zone is 200 - 300 metres.

Programming

Initial Power Up

Note: Depending on the status of the system when it is powered-up, e.g., open tampers etc., some screens may differ from those shown below.

1.Apply battery power first, then connect the mains.

The keypad display shows the Software version number followed by the date.

After 3 seconds, the display shows the time:

16:07

2.Key in the factory default user code (1234) and press Enter.

The display shows one of the following messages depending on how

the system is currently set up:

SYS DIS RST REQ

3.Key-in the factory default installer code zero (0) + 7890, then press Menu.

The display shows:

MENU NO OR LEVEL

8 of 22

496336 Issue 1

Page 8
Image 8
Security Centres 808 manual Programming, Initial Power Up