24
Welding Output AC Power Output
Welding Rod/Current 3-Pase Power use only 1-Phase Power Use only
2.0mm/50A or below 9.5kVA or below 7.6kVA or below
2.6mm/80A 8.6kVA or below 6.8kVA or below
3.2mm/120A 7.2kVA or below 5.7kVA or below
4.0mm ( 2.0mmx2)/170A 5.2kVA or below 4.1kVA or below
5.0mm ( 2.6mmx2)/220A 3.0kVA or below 2.4kVA or below
6.0mm ( 3.2mmx2)/280A 0kVA or below 0kVA or below
( ) indicates 2-Persons Dual Use. (DGW311DM only)
<Caution>
z The simultaneous use of ECO welding and AC power is not available. (DGW311DM only)
DGW311L-(W)380A, DGW311L-(W)400A, DGW311L-(W)415A :
Limitation of AC Power Supply in the simultaneous use of welding and generating (50Hz)
Welding Output AC Power Output
Welding Rod/Current 3-Pase Power use only 1-Phase Power Use only
2.0mm/50A or below 8.5kVA or below 6.8kVA or below
2.6mm/80A 7.6kVA or below 6.0kVA or below
3.2mm/120A 6.2kVA or below 4.9kVA or below
4.0mm/170A 4.2kVA or below 3.3kVA or below
5.0mm/220A 2.0kVA or below 1.6kVA or below
6.0mm/260A 0kVA or below 0kVA or below
11. Checking and Maintenance
Danger : Electric Shock Injuries
z Before performing any equipment check or maintenance, stop the engine, and remove en-
gine key. A person performing the maintenance should always keep the key.
Caution : Fire Burns
z When checking the engine, always stop the engine, and keep away from fire. Wait until the
engine cools down, before performing any checks.
To optimize the use of this equipment, we recommend the periodical equipment checks and
maintenance based on the following matrix.
<Caution>
z The authorized technicians should perform all checking and maintenance work, except for
the pre-startup checks.
z Request for the maintenance item with mark to the authorized distributor or our engi-
neering section.
z This table only covers the simple checks and maintenance for the engine. For more detailed
guide, please refer to the User’s Manual for the engine.
z Always use our genuine replacement parts.