Restart after stopping due to fuel shortage
This equipment is equipped with automatic air vacuuming feature. Therefore, even though the engine stops due to running out of fuel, you can restart the engine easily by the following steps.
①Turn the starter switch to STOP.
② Fill the fuel.
③ Turn the
④ Turn the starter switch to RUN.
⑤ Turn the starter switch to START and drive the starter motor. <Caution>
z Do not drive the starter motor for more than 15 seconds successively. z If you need restart, wait for 30 seconds or more before retry.
⑥ Release the starter switch, as soon as the engine started. <Caution>
z Once the engine is started, do not turn the starter switch to START.
⑦ Wait for about 1 minute to vacuum the air out.
(The engine speed becomes stable when the air is extracted.) <Caution>
z Keep the
7-2 Stopping Generator/Welder
①Turn (Push down) the breaker to OFF.
② Turn the
③ Keep the engine idle (cooling down) for about 5 minutes.
④ Turn the starter switch to STOP.
⑤ After the engine stops, turn the fuel lever to CLOSE. <Caution>
z When the engine does not stop in spite of turning the starter switch to STOP, turn the fuel lever to CLOSE, then the engine will stop in a few minutes.
In this case, consult with our authorized distributor or our engineering section and ask to re- pair.
8.Welding Operation
8-1 Selection – Welding Cable
Select the cable with proper gauge, based on the allowable amperage and distance per the table shown below.
The welding capacity is reduced if the small gauge cable is used. <Caution>
zWelding cables should be used unstrained.
zWhen the welding cables are used in swirl, the welding capacity is reduced.
16