DGW311L-(W)380A, DGW311L-(W)400A, DGW311L-(W)415A :

 

 

Applicable Load (For reference purpose only)

 

(50Hz)

 

 

 

 

 

 

 

 

 

 

Capacity (kW)

 

 

 

 

 

 

 

 

 

Loads

1-Phase

 

1-Phase

3-Phase

(O & U, V, W)

 

(U, V, W)

(U, V, W)

 

 

 

Terminal

Terminal

 

Terminal

Terminal

Terminal

 

1 set

3 sets

 

1 set

3 sets

 

 

 

Total

 

 

Total

 

Electric Bulb, Heater, etc.

3.0

6.0

 

6.0

8.0

-

 

 

 

 

 

 

 

Electric Tools (Series Motor),

1.5

3.0

 

3.0

4.0

-

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

Mercury Bulb (High Power

1.2

2.4

 

2.4

3.2

-

Factor Type)

 

 

 

 

 

 

 

 

 

 

 

 

 

Submersible Pump, Com-

1.2

2.4

 

2.4

3.2

4.0

pressor, etc. (Induction Mo-

 

 

 

 

 

 

tor)

 

 

 

 

 

 

Series Motor: Motor with brush

Induction Motor: Brushless Motor

The value described is OUTPUTfor Induction Motor loads and POWER CON-

SUMPTIONfor the other equipment. <Caution>

zBe sure to use the frequency designated in the equipment incorporated in mercury lamp or induction motor.

zThe load incorporated in motor may require bigger power than the rated power consumption. Therefore, consult with our authorized distributor or our engineering section to clarify.

zWhen connecting 2 or more sets to use, start the load one by one, not to start them simulta- neously.

zWhen switching a Mercury bulb ON again, wait for 15 minutes (about) until it cools down.

zA Mercury bulb may flicker sometimes.

9-3 Operation

Danger : Electric Shock

zBefore connecting or disconnecting a load cable from output terminals, always turn a circuit breaker to OFFposition.

zAll the grounding terminals must be grounded. If one of them is not grounded, human body may get a serious electric shock by leaked current. (Refer to5-3 Earth Leakage Breaker』)

zGrounding should be made after the engine is stopped.

zWhenever the earth leakage breaker activates, you should repair the leaking place first of all.

Caution : Injuries

zBe sure to connect to output terminals or insert a plug to a receptacle, after confirming that all the switches in the loads are positioned to OFF.

22

Page 23