Configuring Your PC
Description The Advance Network Communications Board (ANCB) has a built-in
utility for configuring the unit. The Windows® HyperTerminal program,
which resides on most PCs, can be used to access the utility. Other
serial communication packages that support the following settings can
also be used.
Baud rate: 57.6k baud
Data bits: 8
Parity: none
Stop bits: 1
Flow control: none
Instructions This procedure uses the Windows Hyper Terminal program to configure
your PC to communicate with the ANCB.
1. Click the Start button, and then click on Programs.
2. Click the HyperTerminal icon to start the Program.
Connection Description dialog box will open.
3. In the Name field, type in a Connection Name. Example: Advance
Maxum ANCB.
4. In the Icon field select an Icon to represent the name selected.
22 Data Communications Setup 2000592-001