Information about Software 37
14. Turn off the power to the target domain.
15. Upgrade an on-CMU SPARC64 VI processors to SPARC64 VII processors, or add
SPARC64 VII processors to an existing CMU.
For upgrading the CPU, operate by hot replacement, referring to "6.2 Active
Replacement and Hot Replacement" in SPARC Enterprise M8000/M9000 Servers
Service Manual.
For adding the CPU, operate by hot replacement, referring to "6.2 Active
Replacement and Hot Replacement" in SPARC Enterprise M8000/M9000 Servers
Service Manual.
Note – Do not fail to execute the diagnosis of newly mounted CMU in the maintenance
menu of replacefru(8) command.
16. Confirm that the mounted CPU module has been recognized by the server, and the
error indicator asterisk (*) is not displayed.
17. Confirm no abnormality o ccurred by using showlogs error -v and
showstatus(8) commands.
If you encounter any hardware abnormality of the XSCF contact a service engineer.
18. Move the key position on the operator panel from Service to Locked.
19. In case of addition, sets the following for the CMU.
Set up XSB.
Set up the LSB.
Add the XSB to the domain.
For each setting, see the SPARC Enterprise M4000/M5000/M8000/M9000 Servers XSCF
User’s Guide.
20. Set up and confirm the CPU operational mode of the d omain.
For detail, see the SPARC Enterprise M4000/M5000/M8000/M9000 Servers XSCF User’s
Guide.
XSCF> poweroff -d domain_id
XSCF> showhardconf -M
XSCF> showlogs error -v
XSCF> showstatus