Siemens UM344-2 user manual Symptom Erratic Output, Diagnosing a Defective Digital LCD Meter

Models: UM344-2

1 183
Download 183 pages 46.28 Kb
Page 127
Image 127

UM344-2CALIBRATION AND MAINTENANCE

 

TABLE 6.9 Symptom - Erratic Output

 

 

 

POSSIBLE CAUSE

 

CORRECTIVE ACTION

 

 

 

Loop Wiring

 

Check for 12 Vdc minimum across SIGNAL +/- terminals in transmitter terminal

 

 

compartment.

 

 

Check power supply output voltage: 17 Vdc minimum; 42 Vdc maximum.

 

 

Check for loose loop wiring at power supply terminals, Supply Barriers (if

 

 

used), junction boxes, and transmitter terminal compartment.

 

 

Check for loose leads at Current Sense Resistor.

 

 

Check for accumulation of moisture in transmitter terminal compartment.

 

 

Check for multiple grounds on loop cable shield.

 

 

Check for the proper type of loop cable and for electrical interference between

 

 

the loop cable and any adjacent cables in a cable tray or conduit.

 

 

Check signal loop is grounded, not floating. Ground signal loop at one point

 

 

only, preferably at the power supply negative terminals.

 

 

 

Loop power supply excessively

 

Confirm defective power supply by substituting spare supply for suspect

noisy

 

supply.

 

 

Select a higher damping value (software filter time constant).

High level noise pick-up in sensor

 

Low level leads between sensor and transmitter should be shielded.

leads

 

 

Transmitter Electronics Failure

 

Check transmitter STATUS. If a FAILSAFE message is posted, refer to

 

 

Section 6.3.2.1, paragraph A, for troubleshooting procedures.

 

 

If STATUS is OK, select LOOP OVRD (loop override). Verify loop by setting

 

 

output current to 4, 12 and 20 mA (read on Digital Meter or ammeter connected

 

 

to TEST +/- terminals). Carefully observe that the selected currents remain

 

 

steady.

 

 

If current cannot be set or is unstable, replace the Electronics Module. See

 

 

Section 6.5.

 

 

 

6.3.3 Diagnosing a Defective Digital (LCD) Meter

The optional LCD is functionally tested during a transmitter power up or master reset. It is also tested when the MXC TEST program (transmitter self-diagnostics) is executed. The 4 second test activates all the legends and numerical segments of the LCD. However, if the LCD fails the test, the failure is not reported by the self-diagnostics. The LCD must be observed when performing the MXC TEST program to confirm its test.

If the LCD is not functioning correctly, use an on-hand spare LCD to prove the suspect LCD is defective as follows:

September 1995

6-25

Page 127
Image 127
Siemens UM344-2 user manual Symptom Erratic Output, Diagnosing a Defective Digital LCD Meter