Slant/Fin Hydronic Explorer 2 user manual Floor Profile, Heat Loss Express

Models: Hydronic Explorer 2

1 41
Download 41 pages 49.65 Kb
Page 22
Image 22
Floor Profile

Heat Loss Express

Max Floor Temp (F) – this is a value that you enter to limit the floor temperature. If it is too low, the system may not be able to maintain the required temperature. You can increase this value or provide supplemental heat. Choose a value that is appropriate for the type of floor in the room and that will be comfortable for the occupants. Note that this value must be greater than Room Temperature; otherwise, the radiant tubing will not generate heat.

Floor Temp (F) – this is the actual floor temperature that will be maintained by the radiant tubing system. It may be less than or equal to the Max Floor Temp.

Floor Profile

The Floor Profile pane provides floor profile data. As you change the values for the floor types, the system will recalculate the value in the Radiant Supply Temp (F) box. This is the required water temperature necessary to maintain the Floor Temp value in the Heat Loss – Heated Area pane.

Floor Cover R-Value – allows you to enter the R-value for the type of floor covering. Certain items, when selected, will result the Carpet Pad box being displayed.

Wood Floor R-Value – allows you to enter the R-value for a “finished” wood floor (if used).

Subfloor R-Value – allows you to enter the R-value for the subfloor (if applicable). For applications where the tubing is installed in concrete, gypcrete or mortar, select “Tube in Slab” and then the appropriate selection from the sub-menu. If the tubing is installed under the subfloor, select “Tube Below Wood” and then the appropriate selection form the sub-menus. For applications where the tubing is installed above the subfloor using a “dry” installation technique, select the “Luan Underlayment” option.

Carpet Pad – this box is not displayed when the Radiant Tubing screen is opened. It is displayed only when you select certain items in Floor Cover R-Value, and it allows you to enter the R-value for the pad type used.

Radiant Supply Temp (F) – this is the required water temperature, and it will be recalculated as you enter R-values for the above floor types. Values in excess of 150 oF will be displayed in red to show that the maximum value has been exceeded. If you cannot change the floor profile, you can lower the value by lowering the Max Floor Temp in the Heat Loss – Heated Area pane so that Floor Temp gets lowered. This may result, however, in requiring supplemental heating. Note - changing the tube spacing factor in the Tubing Calculator section does effect this calculation.