VICTORY II VHS Models
Natural Draft Chimney and Type “B” Venting Tables
Table 1. Masonry Vitreous
Chimneys not exposed to the outdoors below the roof line. (5" dia. vent adapter must be used)
| Additional |
|
|
| National Fuel Gas Code |
Boiler | Gas Appliance |
|
|
| Reference Table No.* |
Model(s) † | in Venting System | Connector |
| Requirements* | (ANSI Z223.1) |
No | Type “B” | 1. Connector diameter must be upsized to 7". |
| ||
|
| 2. | Chimney height limits: Min. 15 ft., Max. 30 ft. |
| |
|
| 3. | Lateral length restriction applies (Table | ||
|
| 4. | Internal area of chimney: Min. 50 sq. in., |
| |
|
|
|
| Max. 269 sq. in. |
|
|
|
|
|
| |
No | 1. Connector diameter must be upsized to 7". |
| |||
|
|
| 2. | Chimney height limits: Min. 15 ft., Max. 30 ft. |
|
|
|
| 3. | Max. lateral length may not exceed 2 ft. | |
|
|
| 4. | Internal area of chimney: Min. 50 sq. in., |
|
|
|
|
| Max. 269 sq. in. |
|
|
|
|
|
| |
Yes | Type “B” | 1. See Table |
| ||
|
|
| and connector length restrictions. | ||
|
| 2. | Connector may have to be upsized to 6" diameter |
| |
|
|
| to meet requirement of |
| |
|
|
|
|
| |
Yes | 1. See Table |
| |||
|
|
| and connector length restrictions. | ||
|
|
| 2. | Connector may have to be upsized to 6" diameter |
|
|
|
|
| to meet requirement of |
|
|
|
|
|
|
|
Table 2. Type “B” Venting and
UL LISTED MATERIALS ONLY. (5" dia. vent adapter must be used)
| Additional |
|
| National Fuel Gas Code |
Boiler | Gas Appliance |
|
| Reference Table No.* |
Model(s) † | in Venting System | Connector | Requirements* | (ANSI Z223.1) |
No | Type “B” | See Table |
| |
|
| of vent height and lateral length restriction. |
| |
|
|
| ||
|
|
|
| |
|
|
|
|
|
No | See Table |
| ||
|
| of vent height and lateral length restriction. |
| |
|
|
| ||
|
|
|
| |
|
|
|
|
|
Yes | Type “B” | 1. See Table |
| |
|
| connector length restrictions. |
| |
|
| 2. Connector and vent diameter may have to be | ||
|
| increased to 6" or 7" to meet requirement of |
| |
|
|
| Table |
|
|
|
|
|
|
Yes | 1. See Table |
| ||
|
| connector length restrictions. |
| |
|
| 2. Connector and vent diameter may have to be | ||
|
|
| increased to 6" to meet requirement of |
|
|
|
| Table |
|
|
|
|
|
|
†Only Victory II boiler models shown for each application permitted to be installed in that manner specified.
• Also see Z223.1