Slant/Fin VHS-180, VHS-30 Natural Draft Chimney and Type “B” Venting Tables

Models: VHS-180 VHS-30

1 27
Download 27 pages 46.44 Kb
Page 11
Image 11
Natural Draft Chimney and Type “B” Venting Tables

VICTORY II VHS Models

Natural Draft Chimney and Type “B” Venting Tables

Table 1. Masonry Vitreous Tile-Lined Chimney (not metal lined)

Chimneys not exposed to the outdoors below the roof line. (5" dia. vent adapter must be used)

 

Additional

 

 

 

National Fuel Gas Code

Boiler

Gas Appliance

 

 

 

Reference Table No.*

Model(s) †

in Venting System

Connector

 

Requirements*

(ANSI Z223.1)

VHS-90

No

Type “B”

1. Connector diameter must be upsized to 7".

 

VHS-120

 

 

2.

Chimney height limits: Min. 15 ft., Max. 30 ft.

 

VHS-150

 

 

3.

Lateral length restriction applies (Table 10-3)

10-3 (1999 edition)

VHS-180

 

 

4.

Internal area of chimney: Min. 50 sq. in.,

 

 

 

 

 

Max. 269 sq. in.

 

 

 

 

 

 

VHS-180

No

Single-wall

1. Connector diameter must be upsized to 7".

 

 

 

 

2.

Chimney height limits: Min. 15 ft., Max. 30 ft.

 

 

 

 

3.

Max. lateral length may not exceed 2 ft.

10-4 (1999 edition)

 

 

 

4.

Internal area of chimney: Min. 50 sq. in.,

 

 

 

 

 

Max. 269 sq. in.

 

 

 

 

 

 

VHS-90

Yes

Type “B”

1. See Table 10-8 for chimney height

 

VHS-120

 

 

 

and connector length restrictions.

10-8 (1999 edition)

VHS-150

 

 

2.

Connector may have to be upsized to 6" diameter

 

VHS-180

 

 

 

to meet requirement of 10-8.

 

 

 

 

 

 

VHS-150

Yes

Single-wall

1. See Table 10-9 for chimney height

 

VHS-180

 

 

 

and connector length restrictions.

10-9 (1999 edition)

 

 

 

2.

Connector may have to be upsized to 6" diameter

 

 

 

 

 

to meet requirement of 10-9.

 

 

 

 

 

 

 

Table 2. Type “B” Venting and Metal-Lined Masonry Chimney

UL LISTED MATERIALS ONLY. (5" dia. vent adapter must be used)

 

Additional

 

 

National Fuel Gas Code

Boiler

Gas Appliance

 

 

Reference Table No.*

Model(s) †

in Venting System

Connector

Requirements*

(ANSI Z223.1)

VHS-90

No

Type “B”

See Table 10-1 for minimum and maximum

 

VHS-120

 

 

of vent height and lateral length restriction.

 

VHS-150

 

 

 

10-1 (1999 edition)

VHS-180

 

 

 

 

 

 

 

 

 

VHS-90

No

Single-wall

See Table 10-2 for minimum and maximum

 

VHS-120

 

 

of vent height and lateral length restriction.

 

VHS-150

 

 

 

10-2 (1999 edition)

VHS-180

 

 

 

 

 

 

 

 

 

VHS-90

Yes

Type “B”

1. See Table 10-6 for vent height and

 

VHS-120

 

 

connector length restrictions.

 

VHS-150

 

 

2. Connector and vent diameter may have to be

10-6 (1999 edition)

VHS-180

 

 

increased to 6" or 7" to meet requirement of

 

 

 

 

Table 10-6.

 

 

 

 

 

 

VHS-120

Yes

Single-wall

1. See Table 10-7 for vent height and

 

VHS-150

 

 

connector length restrictions.

 

VHS-180

 

 

2. Connector and vent diameter may have to be

10-7 (1999 edition)

 

 

 

increased to 6" to meet requirement of

 

 

 

 

Table 10-7.

 

 

 

 

 

 

Only Victory II boiler models shown for each application permitted to be installed in that manner specified.

• Also see Z223.1 –– 1999 Chapter 7 and 10.

11

Page 11
Image 11
Slant/Fin VHS-180, VHS-30 installation instructions Natural Draft Chimney and Type “B” Venting Tables