Slant/Fin VHS-30, VHS-180 installation instructions General Troubleshooting Guide For Servicepeople

Models: VHS-180 VHS-30

1 27
Download 27 pages 46.44 Kb
Page 24
Image 24
General Troubleshooting Guide For Servicepeople

VICTORY II VHS Models

General Troubleshooting Guide For Servicepeople

BURNERS FAIL TO OPERATE

 

 

 

CAUSE

 

REMEDY

1.

Gas supply valve shut off

1.

Open gas valve

2.

No power, main electric switch open

2.

Close switch

3.

No power, blown or defective line fuse

3.

Replace fuse

4.

Pilot flame too low

4.

Adjust pilot flame

5.

Flame sensor contaminated

5.

Clean sensor

6.

Roll-out switch open

6.

Replace roll-out switch (inspect flue passages prior to

 

 

 

 

replacement)

7.

Defective air flow switch, restriction or obstruction in

7.

Check air flow switch hose connections. Check for obstruction

 

 

venting system

 

or restriction in venting system. Replace defective switch

8.

Defective blower motor

8.

Check voltage (120V) at motor connector. Replace

 

 

 

 

defective motor

9.

Defective transformer

9.

Replace Aquastat

10.

Defective gas valve

10.

Replace

 

 

 

 

 

BURNERS WILL NOT SHUT-OFF

 

 

 

CAUSE

 

REMEDY

1.

Defective Aquastat

1.

Replace defective Aquastat

2.

Improper wiring or short circuit

2.

Check wiring

 

 

 

 

FLASH BACK-BURNING AT ORIFICES

 

 

 

CAUSE

 

REMEDY

1.

Manifold gas pressure too low

1.

Adjust to proper manifold pressure

2.

Improper primary air adjustment

2.

Adjust air to produce soft, clean flame

3.

Gas regulator bleed too slow

3.

Adjust bleed opening

4.

Burrs on orifices

4.

Remove burrs

5.

Improper orifice

5.

Install proper orifice size

6.

Adverse draft condition in boiler room

6.

Check air supply and venting system

7.

Low main gas pressure

7.

Contact utility

24

Page 24
Image 24