![](/images/new-backgrounds/1055882/5588279x1.webp)
TROUBLESHOOTING GUIDELINES
These guidelines should be utilized by a qualified service agent.
PROBLEMS |
|
| |
| 1.) Blower will not run. |
| |
|
|
| |
| a. “ON/OFF” control switch turned off. | Turn switch to the “ON” position. | |
|
|
| |
| b. Blower unplugged. | Plug blower back into 115 VAC outlet. | |
|
|
| |
| c. No power at outlet. | Repair service to outlet. | |
|
|
| |
| d. Thermostat defective. | Replace thermostat. | |
| e. Control harness defective. | Replace control harness. | |
|
| Reduce the water temperature below 140°F. | |
|
| Turn the power switch to the off position. | |
| f. High limit control circuit open. | Wait 10 seconds. Turn the power switch to | |
| the on position. Reduce the temperature set | ||
|
| point to minimize likelihood of reoccurrence. If | |
|
| this does not solve the problem, replace the | |
NOT ENOUGH HOT WATER |
| thermostat. | |
| g. Blower motor defective. | Replace blower assembly. | |
| 2.) Thermostat problems |
| |
|
|
| |
| a. Thermostat set too low. | Adjust temperature control higher. | |
| b. Thermostat or ECO defective | Replace thermostat. | |
| 3.) Others |
| |
|
|
| |
| a. Heater undersized.. | Reduce hot water use. | |
| b. Low gas pressure | Contact dealer. | |
| c. Incoming water is usually cold. | Allow more time for heater to reheat. | |
| d. Leaking hot water pipes of fixtures. | Have plumber check and repair leaks. | |
| e. Heater not lit or thermostat not on. | Refer to LIGHTING INSTRUCTIONS. | |
VENT PIPE TOO HOT (ABOVE 170°F [77°C]) | Wrong burner orifice. | Turn off heater and gas, clean burner head. | |
| Dirt in burner ports. | Turn off heater and gas, clean burner head. | |
|
| Check exhaust venting and air openings | |
YELLOW FLAME | Combustion air path restricted. | in bottom base pan for obstructions or | |
|
| blockage. | |
CONDENSATION | Water on the floor under heater. | See CONDENSATION section. | |
| Improperly sealed, hot or cold supply | Check for leaks. See Figure 1. | |
| connections, relief valve, drain valve or | ||
WATER LEAKS | thermostat threads. |
| |
Leakage from other appliances or water lines. | Inspect other appliances near water heater. | ||
| |||
| Condensation of flue products. | Refer to CONDENSATION section. | |
| Thermal expansion in closed water system. | Install thermal expansion tank (Do not plug | |
LEAKING T & P | T&P valve). | ||
| |||
Improperly sealed valve. | Check relief valve for proper operation (Do | ||
| |||
| not plug T&P valve). | ||
|
| ||
HOT WATER ODORS | High sulfate or mineral content in water | Drain and flush heater thoroughly then refill. | |
supply. | |||
(refer to cathodic protection) |
|
| |
Bacteria in water supply. | Chlorinate water supply. | ||
| |||
HOT WATER TOO HOT | Thermostat set too high. | Refer to TEMPERATURE REGULATION | |
section. | |||
|
| ||
WATER HEATER SOUNDS | Condensation dripping on burner. | Refer to CONDENSATION above. | |
SIZZLING - RUMBLING | Sediment at bottom of heater tank. | Clean sediment from tank . Refer to | |
DRAINING. | |||
|
| ||
SOOTING | Improper combustion. | Refer to Air Requirements. | |
| Outlet polarity is reversed. | Test polarity and correct. | |
BURNER WILL NOT STAY | High ambient room temperature. | Contact a qualified service agency to | |
| determine cause. | ||
| Defective gas valve. | Replace gas valve. | |
|
|
| |
| Lack of air supply. |
| |
|
|
| |
VENT GAS ODORS | Improperly installed vent piping. | Shut off water heater immediately and contact a | |
Downdraft | qualified service agency to determine cause. | ||
| |||
|
| ||
| Poor Combustion |
|
40