The Redundancy Communications Module (RCM), catalog number IC697RCM711, provides a communications path for sharing data between the two CPUs in the redundant system. In a synchronized system, I/O data is controlled by one unit (the active unit) but is shared between both units (active and backup units). The RCM provides the communications path between the two units. An RCM must be configured in both the Primary PLC and the Secondary PLC. The RCM must reside in rack 0 and there can be no empty slot between the RCM and the CPU (there can be other modules).

RCM Features

The following figure shows the features of the RCM module.

OK

LOCAL READY LOCAL ACTIVE REMOTE READY REMOTE ACTIVE

REDUNDANCY

COMMUNICATIONS

MODULE

a47004

RCM 711

BOARD OK

LOCAL SYSTEM

READY

LOCAL SYSTEM

ACTIVE

REMOTE SYSTEM READY

REMOTE SYSTEM ACTIVE

ON = TRUE DEPRESS 1 SEC. TO SWITCH ACTIVE CPU (MIN 10 SECS BETWEEN SWITCHES)

MODULE FUNCTION

REDUNDANCY COMMUNICA TIONS MODULE.

HIGH SPEED INTERFACE BETWEEN HOT. STANDBY REDUNDANCY SUPPORTED CPUs.

CONNECT TO END

OF EXPANSION BUS

EXPANSION

PORT IN (TOWARDS CPU)

TO BEM711

OR BEM713

(USE TERMINATED CABLE CBL811 OR CBL826)

50 FT. MAXIMUM

CABLE LENGTH FROM BEM 713 TO TO RCM711

UNUSED PORT

DO NOT INSTALL

CABLE OR

TERMINATOR

MODULE IC697RCM711

LABEL:

44A726758±136R02

Figure 5. Redundancy Communications Module - IC697RCM711