Fault Actions in a CPU Redundancy System

Fault actions in the Hot Standby CPU Redundancy System are handled differently than those in a non-redundancy (Simplex) system. Whenever there is a ºreadyº backup unit configured in the system, the fault actions in the active unit will not be those normally specified by the user. For an active unit with a ready backup, any fault which will cause a degradation in performance, or loss of control of I/O which does not cause a similar degradation of performance or loss of control of I/O in the backup will be considered a FATAL fault in the active unit and cause the active unit to transition to STOP mode.

The configurable fault actions will be applied whenever the system is running in stand-alone mode in case you prefer fault tolerance (availability) versus safety (depending on the application). The following tables (1) define the Fault Groups and (2) show the fault groups and their fault action defaults. There are three fault actions shown in Table 11: Fatal, Non-Fatal, and Conditionally Fatal. Fatal always stops the PLC, Non-Fatal never stops the PLC and Conditionally Fatal stops the PLC depending on other information in the fault.

Table 9. Maskable Fault Group Descriptions

 

 

Table

 

 

 

Fault Group

Type

Description

 

 

 

 

 

 

 

 

 

 

 

 

LOSS_RACK

CPU

Lossof or Missing Rack

 

 

 

 

 

 

 

LOSS_IOC

I/O

Loss of or Missing IOC

 

 

 

 

 

 

 

LOSS_IO_MOD

I/O

LossoforMissingI/OModule

 

 

 

 

 

 

 

LOSS_OTHR_MOD

CPU

Loss of or Missing Option Module

 

 

 

 

 

 

 

ADD_RCK

CPU

Addition of or Extra Rack

 

 

 

 

 

 

 

ADD_IOC

I/O

Addition of or Extra IOC

 

 

 

 

 

 

 

ADD_IO_MOD

I/O

AdditionoforExtraI/OModule

 

 

 

 

 

 

 

ADD_OTHR_MOD

CPU

Additionof, Reset of, or Extra Option Module

 

 

 

 

 

 

 

IOC_FAULT

I/O

IOC or I/O Bus Fault

 

 

 

 

 

 

 

IO_MOD_FAULT

I/O

I/OModule Fault

 

 

 

 

 

 

 

CNFG_MIS_MTCH

Both

SystemConfigurationMismatch

 

 

 

 

 

 

 

SYS_BUS_ERROR

CPU

System Bus Error

 

 

 

 

 

 

 

CPU_HARDWR

CPU

CPU Hardware Failure

 

 

 

 

 

 

 

MOD_HARDWR

CPU

Module Hardware Failure (e.g. Serial Port Failure on PCM)

 

 

 

 

 

 

 

IOC_SOFTWR

I/O

IOC Software Failure

 

 

 

 

 

 

 

MOD_OTHR SOFTWR

CPU

Option Module Software Failure

 

 

 

 

 

 

 

PRG_BLK_CHKSUM

CPU

ProgramBlockChecksumMismatch

 

 

 

 

 

 

 

LOW_BATTERY

CPU

Low Battery in the System

 

 

 

 

 

 

 

CNST_SW_EXCD

CPU

Constant Sweep Exceeded

 

 

 

 

 

 

 

PLC_FTBL_FULL

CPU

PLC System Fault Table Full

 

 

 

 

 

 

 

IO_FTBL_FULL

CPU

I/OFault Table Full

 

 

 

 

 

 

 

APPLICATION_FLT

CPU

UserApplicationFault

 

 

 

 

 

 