Press the Esc key twice to save the changes you have just made. This completes the process of converting a Primary PLC redundancy system configuration to a Secondary PLC redundancy system configuration. The differences between the Primary system and the Secondary system are:

1.The CPU module parameter Redund Type in a Primary system is PRIMARY and in a Secondary system is SECNDARY.

2.The Serial Bus Address (SBA) of a redundant GBC in a Primary system MUST be 31 and in a Secondary system MUST be 30.

The Genius Bus Controller bus level display in a Secondary PLC redundancy system is as shown below.

54

Series 90-70 Hot Standby CPU Redundancy User's Guide ± December 1993