2-3 Standard Features

The refrigerant is compressed in the compressor and flows through the discharge line as a gas to the condenser. There it gives up its heat as it condenses to a liquid in the condenser.

An electronic hot gas bypass valve is used to control cooling capacity during intermittent or partial load conditions. This feature contributes substantially to chiller longevity by eliminating excessive cycling of the compressor and providing close temperature control.

2-3 Standard Features

Mechanical Features

Compressor. Hermetic scroll compressors.

Evaporator. Stainless steel copper brazed plate evaporators.

Air-Cooled Condenser. Aluminum fin/ tube with washable filters, package unit only (option on remotes). Variable speed fan control standard for GPAC70 thru 210.

Water-Cooled Condenser. Tube-in-tube condensers (5-15 ton), Shell-and-tube condensers (20-60 ton). All come with electronic cooling water regulating valves. 1 in. NPT valves for GPWC20 & 30; 1.25 in. NPT valves for GPWC40; 1.50 in. NPT valves for GPWC50, 2 in NPT valves for GPWC70 & 90, 2.5 in NPT valves for GPWC105, 3 in NPT valves for GPWC140 & 175, and 4 in NPT valves for GPWC210.

Remote Air-Cooled Condenser. Aluminum fin/tube with low ambient control down to – 20ºF (-29ºC) via a variable-speed primary fan.

Reservoir. 5 hp and 7.5 hp models use a 20 gallon polyethylene tank. 10 hp and 15 hp models use a 40 gallon polyethylene tank.

Piping. Non-ferrous piping

Pump. ODP motors (TEFC Optional)—horizontally mounted stamped stainless steel construction.

Other Mechanical Features

Low process water thermal flow switch

NEMA-rated fan motor(s) on air-cooled models

Galvanized structural steel frame, painted cabinetry, with 4” (locking) swivel casters

Internal process water bypass valve for system protection only

Fully insulated refrigeration and process water piping

20 mesh Y strainer on process water piping into the evaporator

Tank level indication

Pump pressure indication

Electrical Features

Fully accessible NEMA 12-style electrical control enclosure

Single-point power and ground connection

Non-fused disconnect switch, lockable

Branch circuit fusing

GP Series Portable Chillers

Chapter 2: Functional Description

8 of 73

Page 8
Image 8
Sterling 882.93092.00 specifications Standard Features, Other Mechanical Features, Electrical Features