room. Install a liquid line-charging valve to facilitate refrigerant charging. See Figure 3 on page 18 for sizing information. See Figure 5 on page 22 for charge determination.

Discharge Line Sizing. For horizontal runs, the discharge line should be pitched downward, in the direction of flow, at a rate of 1/2” for every 10 feet. This will allow oil to flow towards the condenser. Discharge line sizing is based on the velocity required for sufficient oil return back to the compressor. See