Sterling 882.93092.00 specifications Refrigerant Charge Determination

Models: 882.93092.00

1 73
Download 73 pages 36.77 Kb
Page 22
Image 22

Refrigerant Charge Determination. The approximate amount of refrigerant charge required by the system varies based on the total length of the refrigerant lines and the size of the chiller. Referring to Figure 5, determine the amount of charge based on the horsepower of the chiller and the amount of charge based on discharge and liquid line sizes and lengths. Add these three numbers together to find the final operating charge. The final operating charge must be verified by running the system and checking the liquid line sight glass.

Figure 5: Refrigerant Charge Determination

Line Size

Discharge Line

Liquid Line

OD (inches)

LBS of R-410a

LBS of R-410a

3/8

0.3

3.2

1/2

0.6

6.0

5/8

1.0

9.6

3/4

1.5

14.4

7/8

2.1

20.0

1-1/8

3.7

34.1

1-3/8

5.6

52.0

1-5/8

7.9

73.6

2-1/8

13.7

128.0

2-5/8

21.2

197.4

3-1/8

30.2

281.7

3-5/8

40.9

381.1

4-1/8

53.1

495.4

Note: The amounts listed in Figure 5 are based on 100 feet of pipe. Actual amounts will be in direct proportion to the actual length of the piping.

Oil Charge Determination. The remote air-cooled portable chillers are factory charged with the amount of oil required without field-installed piping. Additional oil required is dependent on the amount of additional refrigerant added.

Calculate the amount of additional oil required by using the following formula:

Pints of oil (Copeland Ultra 22cc) = lbs of R-410a added for field installed piping / 100.