Sterling 882.93092.00 Discharge Line Sizing, GP Series Portable Chillers, Installation, 21 of

Models: 882.93092.00

1 73
Download 73 pages 36.77 Kb
Page 21
Image 21

Figure 4: Discharge Line Sizing

 

 

 

 

 

Horizontal or Downflow Discharge Line Sizes (OD")

 

 

 

 

Circuit

 

 

 

 

Total Equivalent Length (Ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tons

25

50

75

100

125

150

175

200

225

250

275

300

 

5

5/8

5/8

5/8

5/8

3/4

3/4

3/4

3/4

3/4

3/4

3/4

7/8

 

7.5

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

7/8

 

10

7/8

7/8

7/8

7/8

7/8

7/8

7/8

1-1/8

1-1/8

1-1/8

1-1/8

1-1/8

 

15

7/8

7/8

1-1/8

1-1/8

1-1/8

1-1/8

1-1/8

1-1/8

1-1/8

1-1/8

1-3/8

1-3/8

 

20

7/8

1-1/8

1-1/8

1-3/8

1-3/8

1-3/8

1-3/8

1-3/8

1-3/8

1-3/8

1-5/8

1-5/8

 

25

1-1/8

1-1/8

1-1/8

1-1/8

1-3/8

1-3/8

1-3/8

1-3/8

1-3/8

1-3/8

1-5/8

1-5/8

 

30

1-1/8

1-1/8

1-1/8

1-3/8

1-3/8

1-3/8

1-3/8

1-3/8

1-3/8

1-5/8

1-5/8

1-5/8

 

40

1-1/8

1-3/8

1-3/8

1-3/8

1-5/8

1-5/8

1-5/8

1-5/8

1-5/8

1-5/8

1-5/8

2-1/8

 

50

1-3/8

1-3/8

1-3/8

1-5/8

1-5/8

1-5/8

1-5/8

1-5/8

2-1/8

2-1/8

2-1/8

2-1/8

 

60

1-5/8

1-5/8

1-5/8

1-5/8

1-5/8

1-5/8

2-1/8

2-1/8

2-1/8

2-1/8

2-1/8

2-1/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Upflow Discharge Line Sizes (OD")

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit

 

 

 

 

Total Equivalent Length (Ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tons

25

50

75

100

125

150

175

200

225

250

275

300

 

5

5/8

5/8

5/8

5/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

 

 

 

 

 

B-5/8

B-5/8

B-5/8

B-5/8

B-5/8

B-5/8

B-5/8

B-3/4

 

 

 

 

 

 

 

7.5

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

 

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

 

 

 

10

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-3/8

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

 

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

B-3/4

B-7/8

B-7/8

B-7/8

B-7/8

B-7/8

 

 

 

15

7/8

7/8

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

 

 

 

B-7/8

B-7/8

B-7/8

B-7/8

B-7/8

B-7/8

B-7/8

B-7/8

B-1-1/8

B-1-1/8

 

 

 

 

 

20

7/8

7/8

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

A-1/2

A-5/8

A-5/8

 

 

 

B-7/8

B-7/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-3/8

B-1-3/8

 

 

 

 

 

25

1-1/8

1-1/8

1-1/8

1-1/8

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

 

 

 

 

 

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

1-1/8

1-1/8

1-1/8

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

 

 

 

 

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-1/8

B-1-3/8

B-1-3/8

B-1-3/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

1-1/8

1-3/8

1-3/8

1-3/8

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

 

 

 

 

 

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

1-3/8

1-3/8

1-3/8

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

 

 

 

 

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

B-1-3/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

1-5/8

1-5/8

1-5/8

1-5/8

1-5/8

1-5/8

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

A-3/4

 

 

 

 

 

 

 

B-1-5/8

B-1-5/8

B-1-5/8

B-1-5/8

B-1-5/8

B-1-5/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GP Series Portable Chillers

Chapter 3: Installation

21 of 73

Page 21
Image 21