Sterling 882.93092.00 Ethylene Glycol and Propylene Glycol Curves, pump, Gl ycol by Vol um e

Models: 882.93092.00

1 73
Download 73 pages 36.77 Kb
Page 25
Image 25
Figure 6: Ethylene Glycol and Propylene Glycol Curves

Figure 6: Ethylene Glycol and Propylene Glycol Curves

Pe rce nt Glyc ol Cu rves for Free ze P rotec tion

40.0

 

 

 

 

 

 

30.0

 

 

 

 

 

 

20.0

 

 

 

Eth ylene G lycol

 

 

 

 

Prop ylene

Glycol

 

 

 

 

 

 

10.0

 

 

 

 

 

 

0.0

 

 

 

 

 

 

-10.0

 

 

 

 

 

 

-20.0

 

 

 

 

 

 

-30.0

 

 

 

 

 

 

-40.0

 

 

 

 

 

 

-50.0

 

 

 

 

 

 

-60.0

 

 

 

 

 

 

0.0

10.0

20.0

30.0

40.0

50.0

60.0

% Gl ycol by Vol um e

Example: 45°F set point minus 20°F = 25°F.

From Figure 28, 25°F equates to 10% by volume of glycol required.

Note:

The standard pumps used in the GPAC Serice chillers are not recommended to

 

be used with fluid below 0°F (-18°C). Please consult factory for the proper

 

pump.

GP Series Portable Chillers

Chapter 3: Installation

25 of 73

Page 25
Image 25
Sterling 882.93092.00 Ethylene Glycol and Propylene Glycol Curves, pump, Example 45F set point minus 20F = 25F