Sterling 882.93092.00 Calculating Chiller Nominal Flow and Pressure to Process, Pure Water at 40F

Models: 882.93092.00

1 73
Download 73 pages 36.77 Kb
Page 58
Image 58
Pure Water at >40°F

Pure Water at >40°F

 

GPXC-20

GPXC-30

GPXC-40

GPXC-50

 

GPM

DP (PSI)

GPM

DP (PSI)

GPM

DP (PSI)

GPM

DP (PSI)

 

 

 

 

 

 

 

 

 

0.5X Nominal

6

1.7

9

1.7

12

1.6

18

1.8

1.0X Nominal

12

5.9

18

6.1

24

5.8

36

6.4

2.0X Nominal

24

21.4

36

21.9

48

20.7

72

23.3

 

 

 

 

 

 

GPXC-70

GPXC-90

GPXC-140

GPXC-175

0.5X Nominal

24

1.7

30

1.8

36

1.7

48

1.8

1.0X Nominal

48

6.1

60

6.5

72

6.1

96

6.4

2.0X Nominal

96

21.9

120

23.5

144

22.1

192

23.6

 

 

 

 

 

 

 

 

 

GPXC-210

 

 

 

 

 

 

0.5X Nominal

72

1.7

 

 

 

 

 

 

1.0X Nominal

144

6.2

 

 

 

 

 

 

2.0X Nominal

288

22.7

 

 

 

 

 

 

Calculating Chiller Nominal Flow and Pressure to Process

Flow rate: Obtain the flow reading from the appropriate pump curve.

Pressure: Obtain a corresponding pressure reading from the pump curve you selected, then subtract the one-pump pressure drop listed in the above table using the appropriate chiller hp and flow rate.

GP Series Portable Chillers

Chapter 7: Appendix

58 of 73

Page 58
Image 58
Sterling 882.93092.00 specifications Calculating Chiller Nominal Flow and Pressure to Process, Pure Water at 40F