208-230/3/60, 460/3/60, 575/3/60 volt; 400/3/50 volt

Refrigeration Features

HFC-410a refrigerant

Electronic hot gas bypass capacity control

High refrigerant pressure cutout switches

Suction and discharge pressure transducers.

High pressure spring actuated relief valve

Multiple refrigeration access ports

Liquid line shut-off ball valves

Filter-dryer

Sight glass

Externally equalized thermal expansion valve

Liquid line solenoid

Compressor crankcase heater

Controller Features

Off-the-shelf microprocessor-based PID controller with To Process, From Process and Set Point readout

Time delay for proof of water flow/pressure (models w/pump only)

Low refrigerant pressure time delay for low ambient start-up on remote air-cooled and air-cooled chillers with the variable-speed fan option.

8 line x 20 character display with status, alarm, and service screens

Other Features

One year labor warranty and one year compressor warranty

Two year parts warranty

Two year limited controller warranty

2-4 Safety Devices and Interlocks

Caution! Protect the system from freezing with glycol 20ºF below the leaving water temperature set point. Condensation may form inside the pump tank and dilute the mixture, therefore the freezing point should be verified periodically. See Figure 6 on page 18 for the correct mixture.

Crankcase Heater

All of the chillers are equipped with a compressor crankcase heater. It is wired through the control transformer that operates continuously whenever power is applied to the chiller.