Sterling SDA 150-380 E5CK Operating Parameters, Available E5CK Modes, Menu Display Level 0 Mode

Models: SDA 150-380 90-225 CFM

1 52
Download 52 pages 28.89 Kb
Page 21
Image 21

E5CK Operating Parameters

The E5CK has several mode selections. Within each mode are numerous parameters that can be set. The setting is different for the temperature control unit and the dew point display.

Before you can access the several modes of operating parameters, you must change the security lock-out of the controller. The factory sets the security level to protect the parameters from being accidentally changed. Below is an explanation of the operating modes, how to change out the security level and the factory default settings.

Available E5CK Modes

Menu Display

Level 0 Mode

For normal operation. Execute AT auto-tuning, change to manual mode.

Level 1 Mode

For adjusting primary control parameters. Execute: Set alarm values; set the control period; set PID parameters.

Level 2 Mode

For adjusting secondary control parameters. The dehumidifying dryer uses E5CK default settings.

Setup Mode

For setting the basic specifications. Set parameters for input type, scaling, output assignments and direct/reverse operation.

Expansion Mode

For setting expanded functions. Set: ST (self-tuning), SP setting limiter. Select: advance PID or ON/OFF control.

Option Mode

This mode is only accessible when and option board is installed.

Calibration Mode

For calibrating communication unit E53-CKF. Not used.

Manual Mode

Sets the controller to manual operation mode. Not used on dehumidifying dryers.

Cabinet Series Dehumidifying Dryer

20

Page 21
Image 21
Sterling SDA 150-380 E5CK Operating Parameters, Available E5CK Modes, Menu Display Level 0 Mode, Level 1 Mode, Setup Mode