Sterling SDA 150-380, 90-225 CFM installation manual Level, Parameter, Factory

Models: SDA 150-380 90-225 CFM

1 52
Download 52 pages 28.89 Kb
Page 47
Image 47

Level 2

Cn5L input shift lower limit

 

-999.9 to 999.9°C

0.0

Default

 

 

 

 

 

Mode

Parameter

Setting range

Default

Factory

 

 

 

 

 

 

setting

Setup

Cn-t Input Type

0 to 21

2

17

Setup

Cn-H Scaling Upper Limit

Scaling Lower Limit +1 to

-100

15°F/-9C

9999 EU

 

 

 

 

 

 

Setup

Cn-L Scaling Lower Limit

-1999 to SP Setting Upper

0

-40°F/-40C

Limit –0.1 EU

 

 

 

 

 

 

Setup

dP Decimal Point

0 to 3

0

Default

Setup

CnCE Parameter Initialize

Yes/No

No

Default

Setup

6Ut1 Control Output 1

Heat/Cool/Alarm 1/Alarm 2/

Heat

COOL

Assignment

Alarm 3/LBA

 

 

 

 

Setup

6Ut2 Control Output 2

Heat/Cool/Alarm 1/Alarm 2/

AL-1

Default

Assignment

Alarm 3/LBA

 

 

 

 

SetUp

Sub 1 Auxiliary Output 1

Alarm 1/Alm 2/Alm 3/LBA/S.

AL-2

Default

Assignment

ERR/E333

 

 

 

 

Setup

ALt1 Alarm 1 Type

0 to 11

2

8

Setup

AL1n Alarm 1 open in alarm

NO/NC

NO

Default

Setup

ALt2 Alarm 2 Type

0 to 11

2

8

Setup

AL2n Alarm 2 open in alarm

NO/NC

NO

Default

Setup

6rEU Direct/Reverse

OR-R/OR-D

OR-R

Default

Operation

 

 

 

 

 

Expansion

SL-H Set Point Upper Limit

SP Lower Limit +1 to

1300

15°F/-9C

Scaling Upper Limit

 

 

 

 

 

 

Expansion

SL-L Set Point Lower Limit

Scaling Upper Limit to Sp

-200

-40°F/-40C

Lower Limit

 

 

 

 

 

 

Expansion

CntL PID/ON/OFF

PID/ON-OFF

PID

ON-OFF

Expansion

rESt Standby Sequence

0/1

0

Default

 

 

Reset Setting Method

 

 

 

Expansion

rEt Automatic Return of

0 to 99 SEC

0

Default

 

 

Display Mode

 

 

 

6-8 Restoring the E5CK Temperature Controller and Dew Point Meter to Factory Setup

If preset parameters on the controller have been tampered with and it no longer properly controls temperature and displays dew point, you can restore the controller to factory setup.

Cabinet Series Dehumidifying Dryer

46

Page 47
Image 47
Sterling SDA 150-380, 90-225 CFM installation manual Level, Parameter, Factory