SITE REQUIREMENTS
1. FLUE OUTLET POSITIONS
Terminal
Flue
Vertical
Measurement
Horizontal
Measurement
150mm
max
Adjacent
Building
Insulation
|
|
| The vertical measurement is the lowest from either the | ||
|
|
| point of discharge or 150mm above insulation. | ||
|
|
|
|
| |
| Position On Roof | Minimum Clearances |
| IMPORTANT: Seek specialist | |
A | On ridge or within 600mm | 600mm above ridge |
| advice if installing in a dwelling | |
| with a thatched roof | ||||
B | Elsewhere on roof | 2300mm horizontally from roof surface and: | |||
| |||||
|
| a) 1000mm above highest point of flue exit |
|
| |
|
| from roof or |
|
| |
|
| b) as high as the ridge |
|
| |
C | On pitched, within 2300mm horizontally to | 1000mm above top of opening |
|
| |
| openable window, dormer |
|
|
| |
D | Within 2300mm of another building | 600mm above top of building |
|
|
2. HEARTH DIMENSIONS
150mm | 150mm |
minimum | minimum |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Constructional | 225mm |
|
|
|
| ||
150mm |
|
| |||||
Hearth 840mm | minimum |
|
| ||||
minimum |
|
| |||||
minimum |
|
|
|
| |||
|
|
|
| Constructional | |||
|
|
|
|
|
| ||
|
|
| Change in level to | Hearth 840mm | |||
|
|
| minimum | ||||
|
|
| mark safe perimeter | ||||
|
|
|
|
|
2.1The appliance must stand on a constructional hearth with the minimum dimensions as shown in the diagram below.
2.2The building must have a suitable
•Consult a structural engineer for advice before proceeding
2.3When fitting into an existing hearth check:
•that the appliance complies with current construction regulations and is at least the minimum sizes shown
2.4If there is no existing fireplace or chimney it is possible to construct a suitable
•Check if adding a new chimney to your property requires planning permission
PR8077