STUDER INNOTEC HP-COMPACT
User manual HP-COMPACT V3.0 E 19
1 2 3 4
ON/OFF
! -batt !
Remote control
60V/0,5A
max.
Remote control
COMPACT
only
Dry contact
4.9 The Remote Control
As an option, a Remote Con-
trol can be connected to the
HP-COMPACT. All ope-
rating controls and displays
except from level adjustment
are available on the Remote
Control. The Remote Control
is supplied with a 20m long
cable. It can as long as 40m.
The Remote Control is sui-
table for surface mounting on
the wall or on to a switch
board. It is fixed with 4
screws. The HP-COMPACT
can also be programmed
with the Remote Control.
The Programming is descry-
bed in the section „Program-
ming“.
The output power and the
charging currents are dis-
played on the Remote Control.
In the Remote Control there is
an additional Alarm Contact
and a built-in Control Input.
These two functions are avai-
lable through Tip-jack RJ11/4
for use. This Auxiliary Contact
is Front / Work Contact (max.
0.5A!), which is independent
from the Auxiliary Contact of
the HP-COMPACT. This con-
tact is active in case of an
alarm of the HP-COMPACT.
The Control Input is connected in parallel to the ON/OFF- push button. The HP-COMPACT
can be switched on or off through this input with an impulse button or an impulse contact.
Order Number for Remote Control: RCC-01
Dimensions: H x B x T / 111.5 x 136.5 x 25mm
Caution: No external voltage should be connected to this Input Control.
4.10 The Temperature sensor
Operating voltage of lead-acid batteries change depends on
the temperature. To correct the operating voltages accord-
ing to the actual temperatures, a temperature sensor can be
connected to the HP-COMPACT.
The compensation through the sensor is –3mV/°C/Cell.
Order Number: CT-35
Dimensions: H x B x T / 58 x 51.5 x 22mm
OFF
AC OUT
Over Temp.
Overload
A
C IN
SOLAR CHARGE
Contact manual
Contact active
Program

COM PAC

T

A
UXILIARY CONTACT ON/OFF
INVERTER - CHARGER
(Select)
RCC-01
INVERTERCHARGER
(Program) (Change status)
Battery
Low/High
RESET
ALARM
10
20
30
40
50
60
70
TRANSFER
Ch
arg
er
Inv
ert
er
5
10
20
40
60
80
100
130
160
A
%
EQUALIZE
160
80
90
100