STUDER INNOTEC

HP-COMPACT

8 Technical Data

 

Model

HPC2512

 

HPC4024

 

HPC5048

 

HPC7048

 

Inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal battery voltage

12 V

 

24 V

 

 

48 V

 

48 V

 

 

Input voltage range

9.5 – 17 V

 

19 – 34 V

 

 

38 – 68 V

 

38 – 68 V

 

Nominal power @ 25°C

2500 W

 

4000 W

 

 

5000 W

 

7000 W

 

Maximum load 30 min. @ 25°C

2800 W

 

4500 W

 

 

6000 W

 

8000 W

 

Maximum load 5 sec

 

 

 

3 x

Pnom

 

 

 

 

Maximum load

 

 

 

up to short circuit

 

 

 

Maximum asymmetric load

 

 

 

up to Pnom

 

 

 

Standby adjustment

 

 

 

1 to 25 W

 

 

 

Cos ϕ

 

 

0.1 - 1

 

 

 

 

 

Maximum efficiency

93 %

 

 

94 %

 

96 %

 

96 %

 

 

Consumption OFF/Standby/ON

1.4/1.8/10 W

 

1.7/2/16 W

 

 

2/2.5/18 W

 

2/3/25 W

 

Output voltage

 

 

 

230 Vac

 

(0 / - 10%)

 

 

 

 

Output frequency crystal controlled

 

 

 

50 Hz

± 0.05 %

 

 

 

 

Total harmonic distortion

 

 

< 2%

 

 

 

 

 

Dynamic behaviour on load change 0 100 %

 

 

 

0.5 ms

 

 

 

Overload and short circuit protection

 

 

Automatic disconnection with 3 time restart attempt

 

 

 

Overheat protection

 

Acoustic warning before shut-off - with automatic restart

 

Battery charger (4 STEP) I-U-Uo-Equalize (every 25 cycles)

 

 

 

 

 

 

 

 

 

Charging current adjustable

0 – 110 A

 

0 – 100 A

 

 

0 – 70 A

 

0 – 90 A

 

Input current balance adjustment (Power Sharing)

1 – 30 A

 

1 – 30 A

 

 

1 – 30 A

 

1 – 50 A

 

Maximum input voltage

 

 

 

265

Vac

 

 

 

 

Minimum input voltage

 

 

 

Adjustable threshold from 150 to 230 Vac

 

 

 

Input frequency

 

 

 

45 – 65 Hz

 

 

 

Power Factor Correction (PFC)

 

 

 

EN 61000-3-2

 

 

 

Battery control (thresholds and times adjustable by the user)

 

 

 

 

 

 

 

 

 

Absorption time

 

 

 

 

0-4h

 

 

 

End charge cycle voltage

14.4 V

 

28.8 V

 

 

57.6 V

 

57.6 V

 

Floating voltage

13.6 V

 

27.2 V

 

 

54.4 V

 

54.4 V

 

Equalisation voltage

15.6 V

 

31.2 V

 

 

62.4 V

 

62.4 V

 

Deep-discharge protection

10.8 V

 

21.6 V

 

 

43.2 V

 

43.2 V

 

Temperature compensation (option CT-35)

 

 

 

-3mV / °C /

cell

 

 

 

 

General data

 

 

 

 

 

 

 

 

 

 

 

Multifunction contact - potential free (3 points)

 

 

 

16 A – 250 Vac

 

 

 

Max. current on transfer relay

30 A / 6.9 kVA

 

30 A / 6.9 kVA

 

 

30 A / 6.9 kVA

 

50 A / 11.5 kVA

 

Transfer time

 

 

 

< 20 ms

 

 

 

 

 

Weight

33 kg

 

39 kg

 

 

41 kg

 

48 kg

 

Dimension h x l x L [mm]

242/288/480

 

242/288/480

 

242/288/480

 

242/288/500

 

IP protection index

 

 

 

IP 20

 

 

 

 

 

EEC conformity

EN50081 I/II, EN 55014 – EN 55022, EN 61000-3-2

 

 

 

IEC 801 I/II/III/IV, CEI 555, IEC 1000-3-2, LVD 73/23/EEC

 

 

 

 

 

 

 

Working range

-20 to 55°C

 

 

 

 

 

 

 

 

 

Ventilation

from 45°C

 

 

 

 

 

 

 

 

 

Acoustic level without / with ventilation

< 10 dB / < 35 dB

 

 

 

 

 

 

 

 

 

Recommended battery capacity (C10)

> 5 x Pnom/Unom

 

 

 

 

 

 

 

 

 

Warranty

2 years

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

 

 

 

 

Remote control (112 x138 x 25mm / 20 m cable)

RCC-01

 

 

 

 

 

 

 

 

 

 

Remote power sharing (20 m. cable)

RPS-01

 

 

 

 

 

 

 

 

 

 

Battery temp. sensor (58 x 51.5x 22mm / 3 m cable)

CT-35

 

 

 

 

 

 

 

 

 

Data may change without any notice

User manual

HP-COMPACT V3.0 E

25

Page 25
Image 25
Studer Innotec user manual Technical Data, HPC2512 HPC4024 HPC5048 HPC7048