4.6.3 Input current repartition (Power sharing)
To manage the power available on the AC INPUT (depends on the supply use) the HP- COMPACT is equipped with a system usually called “Power sharing” or INPUT power dis- tribution. With this function it is possible to limit the AC INPUT current assigned to the charger. The more current it uses on the OUTPUT the less it gives to the charger. Priority to the OUTPUT. When the power sharing is used the LED 200% (red) is lit to point out that the charge is limited.
Caution: if the power use on the OUTPUT is higher than the value of the INPUT LIMIT (26) the
4.6.3.1 Set the INPUT LIMIT (26) |
|
| |
The current available for the | Generator | Current | |
supply used from a motor generator, the network of a camp- | power | (230V) | |
ing or of a shore connection. The value of the turning knobs | 500W | 2A | |
INPUT LIMIT (26) must be adjusted lower or equal to the cur- | 900W | 4A | |
rent available from the source. | 1500W | 6.5A | |
For example if you have a generator of 2kW you must adjust |
|
| |
2000W | 8.5A | ||
the turning knobs 26 to a max. 8.5A. To calculate this, one |
|
| |
3000W | 13A | ||
divides the nominal power (2000W) by the voltage (230V). If |
|
| |
5000W | 21A | ||
|
you have a circuit breaker (i.e. 6A) before the
This adjustment can be done remotely with the optional
4.6.4 Charging current
The maximum charging current for the battery can be adjusted with the Turning Knob 22 (CHARGER). The charging current of the battery should be set to approximately 10 – 20% of the battery capacity (at C10). This means that the charging current for a battery with 300Ah should be set between 30 – 60A.
The charging current is displayed on POWER MONITOR (25) of the front panel or on the Remote Control.
4.6.5 Battery Condition
Notice: the exact measure of the battery state of charge with electrical parameters is al- most impossible. The display of the state of charge is always more or less precise. The measure system built in the
User manual | 16 |