| Maximum |
| |
|
|
| Oil Burner | Time Delay | Minimum | |
| Potential/Frequenc | Supply/Return | Assembly | Type Fuse | Recommende | |
Model | Air Blower Full | Full Load | or Inverse | d 75 deg. C. | ||
y/No. of Phases | Load Current | Current | Time | Copper | ||
| (V/Hz/Ph) | (Amps) @ 115 | Circuit | |||
| (Amps) @ | Power Wiring | ||||
|
| VAC | 115 VAC | Breaker | Size (AWG) | |
|
|
| Size | |||
|
|
|
|
| ||
|
|
|
| (Amps) |
| |
OD6**072D48 | 120/60/1 | 7.5 PSC | 1.7 | 15 | 12 | |
OD6**072DV5 | 10.1 ECM | 15 | 12 | |||
|
|
Table 10: Typical Electrical Requirements for Various OD6 Models
Wire size selections in Table 10 are based upon Table
NOTICE: Before the unit is started, the installer and/or electrician must check the following items:
1.Check every electrical connection of
2.Review wiring diagram for proper routing and connection of all field wiring.
3.All wiring sizes must comply with local codes or the National Electrical Code. To minimize voltage drop to the appliance, the next larger size wire should be used when long wiring runs, in excess of 100 ft., are employed. Refer to the wiring diagrams when wiring or servicing.
In the event a circuit breaker trips or a fuse blows as a result of the operation of this appliance, investigate the appliance electrical system to determine the cause. Correct any electrical faults and abnormal conditions before putting the unit back into operation. Do not put in a larger fuse and do not exceed maximum fuse size listed on the rating label in order to temporarily “fix” the problem. The rating label is located on the inside of the burner compartment cover.
Electronic Air Cleaner (EAC) and Humidifier Installation:
The fan timer on this unit has designated terminals to control the operation of an electronic air cleaner and/or humidifier. These terminals provide line voltage for the control of these accessories, refer to Figure 15 on the next page. Connection between EAC and N6 provides a switched 115 vac to power an electronic fan cleaner. The same switched 115 vac is available between EAC and N7 and may be used in conjunction with a humidistat to control a humidifier. These terminals are energized whenever the blower is active.