Thermo Products OD6RA072D48B, OD6FA072DV5R 1st STAGE ADJUSTMENT, 2nd STAGE ADJUSTMENT

Models: OD6FA072D48B OD6FA072DV5B OD6RA075DV5R OD6FA072D48R OD6RA072D48R OD6RA072D48B OD6FX072DV5R OD6RA072DV5B OD6RX072DV5R OD6FA072DV5R

1 76
Download 76 pages 60.97 Kb
Page 44
Image 44
1st STAGE ADJUSTMENT:

Figure 22

1st STAGE ADJUSTMENT:

Adjustment of air shutter: place the small plug (9) of the economizer (10) into the position I (Item A). In this way the burner will remain permanently in the 1st stage.

Loosen the nut (2), turn the screw (3) until the air shutter (1) reaches the position desired. Then lock the nut (2).

Pressure regulation: this is set at 130 psi at the factory. Should such pressure be reset or changed, just turn the screw (4). The pressure gauge must be mounted in place of cap (5).

2nd STAGE ADJUSTMENT:

Adjustment of air shutter: place the small plug (9) of the economizer (10) into the position II (Item B). In this way the burner remains permanently in the 2nd stage. Loosen the nut (6), turn the screw (7) until the air shutter (1) reaches the position desired. Then lock the nut (6).

Pressure regulation: this is set at 170 psi at the factory. Should such pressure be reset or changed, just turn the screw (8). The pressure gauge must be mounted in place of cap (5).

i.SMOKE: A smoke sample should be drawn from the heat exchanger flue passageway, which is covered by the vent terminal. (Remove a large machine screw from the front face of the vent terminal for direct access to the flue through the opening.) If the first smoke reading is zero (0), close the air band, or shutter, on the burner until a trace smoke reading is measured.

NOTICE: To achieve proper combustion and the efficiencies listed in sales brochures, instruments must be used to secure CO2 or O2 readings.

41

Page 44
Image 44
Thermo Products OD6RA072D48B, OD6FA072DV5R, OD6RX072DV5R, OD6RA072DV5B 1st STAGE ADJUSTMENT, 2nd STAGE ADJUSTMENT